Technical Data - Quick TCD 1022 D Manual De Instalacion Y Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

N. OF
PROBLEM
FLASHES
1
Overload on the
command electrical
line
2
Interruption on the
command electrical
line
3
Problem present on
the BTR* propeller.
4
Problem present in the
parallel/series switch*
5
Problem present on
TMS*
* If installed.
The resetting of this class of problems occurs, once the cause that has generated them has been removed, by
switching off and switching back on the remote control.
When problems 3, 4, 5 are present, it may be necessary to turn off and turn back on the external devices that
signalled the problem. Refer to their installation and use manual.
MAINTENANCE
The control panel needs no particular maintenance. To ensure optimum performance from the equipment, once a
year check the cables and the electrical connections.
Clean the control panel with a soft cloth dampened with water. Do not use chemical or abrasive products to clean
the control panel.

TECHNICAL DATA

MODEL
OUTPUT CHARACTERISTICS
Current capacity of right or left thruster commands.
INPUT CHARACTERISTICS
Supply voltage (1)
Quiescent current (2)
Maximum current absorption (3)
AMBIENT CHARACTERISTICS
Operating temperature
Protection rating (4)
GENERAL CHARACTERISTICS
Dimensions including frame (L x L)
Weight
EMC class
(1)
With power supply voltage less than 8 Vdc the control panel can reset.
(2)
Typical value with control panel disabled.
(3)
Typical value with control panel enabled and one direction button pressed.
(4)
Excluding the back of the control panel (IP20).
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions:
1)
This device may not cause harmful interference, and
2)
this device must accept any interference received including interference that may cause undesired operation.
®
QUICK
RESERVES THE RIGHT TO MODIFY THE TECHNICAL CHARACTERISTICS OF THE EQUIPMENT AND THE CONTENTS OF THIS MANUAL WITHOUT PRIOR NOTICE.
TCD1022 D/1042 D - REV004A
SYSTEM PROBLEMS - TECHNICAL DATA
DESCRIPTION
The problem is signalled when the control detects a short circuit or an overload on the command
electrical line of the propeller. Check the wiring of the electrical line of the remote control to
the propeller and the absorption of the remote control switches installed on the propeller.
The problem is signalled when the control detects an interruption on the command electrical
line of the propeller.
Check the wiring of the electrical line of the remote control to the propeller.
The control system of the BTR propeller has detected a problem.
Refer to the BTR use and maintenance manual.
The control system of the PSS switch has detected a problem. Refer to the PSS use and
maintenance manual.
The TMS line switch has detected a problem connected to the remote control switch of the
propeller. Refer to the TMS use and maintenance manual.
TCD 1022
4A max
from 8 to 31 Vdc
10 mA
55 mA + absorption of remote control coil
from -20 to +70 °C
IP 66
78 mm x 78 mm
80 g
EN 60945 - FCC TITLE 47 Part 15 SUBPART B CLASS B
GB
TCD 1042
78 mm x 78 mm
140 g
23

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Tcd 1042 dTcd 1022 eTcd 1042 eThruster command tcd 1022 dThruster command tcd 1042 d

Tabla de contenido