Drain joint installation

(see fig. 14)
Fit the seal into the drain elbow, then insert the drain joint into the base pan hole in the bottom of the out-
door unit, rotate 90° to assemble them securely. Connect the drain joint with an extension drain hose (not
included). In this way condensed water, which is produced during heating mode of the airconditioner, can
be drained away.
3.03
Seal
Drain joint
www.zibro.com/download
S1825 - S1833 - S1847
Installation & Service Manual
Fig. 14
For SC30xx models
≥ ø85 mm
< 20
< 20
≥ 20
≥ 20
cm
cm
cm
cm

REFRIGERANT PIPING CONNECTION

ATTENTION
All refrigerant work and refrigerant piping should comply with the local legislation, standards
and codes and should only be done by qualified and skilled people.
CAUTION
For your safety, always wear safety eye wear and work gloves when connecting the pipes.
4
74
Base pan hole of
outdoor unit
Seal
Drain pipe
The last 20 cm of the
refrigerant pipe, close to
the connector must be
kept straight. Bending can
cause leakage and is not
covered by the warranty.
Fig. 15