Standard impulsive mode
The relay remains active as long as the button is being
pressed or as long as the tag remains in the vicinity
of the reader.
Automatic impulsive mode
The relay remains active for 2 seconds and is then
automatically released.
9. Setting the relay logic mode
• Switch off the power to the interface.
• Set the dips according to the table.
Relay output mode
OFF
Dip #1 NO Output relay 1
Dip #2 NO Output relay 2
Dip #3 NO Output relay 3
Dip #4 NO Output relay 4
• Press and hold down button P2;
• Power up the interface;
• The interface will sound 2 long 'beeps'.
The parameters have been set
ON
NC Output relay 1
NC Output relay 2
NC Output relay 3
NC Output relay 4
30
10. Setting the relay output mode
• The jumpers J1, J2, J3 and J4 are
J1
Pos.1 Pos.2
used to set the corresponding relays:
J2
J3
CHA, CHB, CHC, CHD
J4
• The relays activation will be ON/OFF
when the jumper is in position 1.
• The relays activation will be
IMPULSIVE when the jumper is in
position 2.
11. Setting the remote RFID reader
dip 1 dip 2
OFF OFF buzzer OFF - backlight OFF
ON
OFF buzzer ON - backlight ON - event
OFF
ON buzzer ON - backlight ON - low
ON
ON buzzer ON - backlight ON - high
event: the indications are activated when a tag is detected
(1)
low: backlighting always active at low intensity
(2)
high: backlighting always active at high intensity
(3)
To access the selection dips, rremove the four
screws "A" fig. 4 and remove the electronic card
protection panel.
Indicator modes
(2)
(1)