DALIeco Control
3
Function and external components
3.1 Fundamental operating principle
The control unit changes/switches the lighting at workplaces, in corridors and other common
rooms depending on the usable daylight and the presence/motion of persons. This is recorded
by sensors. This increases working comfort and saves energy. There are function modes for vari-
.
ous applications/scenarios
8
These can be adapted individually
5.
3.2 DALI 1 / DALI 2 twin-channel control
The luminaires can be operated with identical light values or with OFFSET for CH-2 after electri-
cal installation to the DALI 1 (CH-1) and DALI 2 (CH-2)
3.3 External push-button
4
Actuation of an external push-button has priority over automatic functions.
3.4 Behavior after mains interruption
Depending on the set function mode, the system is in preset condition when mains voltage is
restored:
Operating mode
Single Offi ce
Open Plan Offi ce
Corridor
Meeting room/classroom
Sanitary Room
Staircase
26
5.10.
Condition
OFF
OFF
STANDBY
LAST STATE
STANDBY
STANDBY
4
Operation
A description of all push-buttons/LEDs of the master remote and their functions and a descrip-
tion of all push-buttons/LEDs of the user remote and their basic functions.
4.1 Master Remote remote control
Push-buttons / LEDs / connections
(1)
[ON/OFF] Lighting on/off
(2)
Signalization LED 1 (green/red/orange)
(3)
[test] Test mode for setting detection range (1 second delay time)
(4)
[Function modes] selection
(5)
[PROG] Programming mode on/off
(6)
[100 h Burn-in] on/off
(7)
[Auto setup] Activation of automatic set value saving
(8)
[CH-1] Setting brightness on channel 1 (manual/direct)
(9)
[Stand-by-time] Selection of STANDBY time defaults
(10)
[Sensor select] Sensor selection
(11)
Signalization LED 2 (green/red/orange)
(12)
[Switch off delay] Selection of delay time defaults
(13)
[Macro Recorder] Recording/saving/sending push-button sequence
(14)
[Offset] Setting OFFSET on/off
(15)
[PC modes] No function
(16)
[CH-2] Setting brightness on channel 2 (manual/direct)
(17)
[Manual setup] Manual light value setting
(18)
[Stand-by-level] Selection of STANDBY defaults
(19)
/
Selection of daylight/motion sensor functions on/semi-automatic/off
(20)
Connection USB mini
Signalization LEDs
•
LED 1
- flashes rapidly during signal transfer (IR) (green)
•
LED 1
- flashes in "PROG" mode (red)
•
LED 1
- lights up during USB transmission (orange)
•
LED 2
- flashes in "Sensor Select" mode (green)
•
LED 2
- flashes while recording the macro recorder (red)
•
LED 1/LED 2 - lights up during "Reset" Master Remote (orange)
(and
separate instructions)
7
GB