Descargar Imprimir esta página

Independent Operation Of Several Systems; Reset; System Reset (Using Master Remote); Reset Master Remote - Osram DALIeco Control Manual De Instrucciones

Ocultar thumbs Ver también para DALIeco Control:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

DALIeco Control

7.4 Independent operation of several systems

Teaching of the User Remote to a specifi c selected receiver in order to permit independent
operation of several systems (maximum 15) in the same room.
1.
Simultaneously press push-buttons [CH-1
(VLP) to start individual programming (LED fl ashes red).
2.
Activating number block (factory setting = 16):
- Number block 1-4: Press push-button [1] (SP).
- Number block 5-8: Press push-button [2] (SP).
- Number block 9-12: Press push-button [3] (SP).
- Number block 13-16: Press push-button [4] (SP).
3.
Programming system number:
- Press push-button [1], [2], [3] or [4] (SP) for the system
number to be programmed (factory setting = 16) (LED
fl ashes green twice and system fl ashes in confi rmation).
--> Example: Programming system number 10:
1.
Simultaneously press push-buttons [CH-1
2.
Press push-button [3] (SP) to activate number block 9-12.
3.
Press push-button [2] (SP) to program system number 10
(LED fl ashes green twice and system fl ashes in confi rmation).
8

Reset

8.1 System reset (using Master Remote)

1.
Press push-button [PROG] (LP) to start programming mode (LED1 fl ashes).
2.
Press [Single Offi ce] (SP) to set default function mode (LED1 fl ashes rapidly).
3.
Press push-button [PROG] (SP) to exit programming mode.

8.2 Reset Master Remote

1.
Press push-button [PROG] (LP) to start programming mode (LED1 fl ashes).
2.
Simultaneously press (VLP) [Corridor] and [Staircase] (LED2 fl ashes).
3.
Press push-button [PROG] (LP) – (LED1 and LED2 light up orange for 3 seconds).

8.3 Reset User Remote

1.
Simultaneously press (VLP) [CH-1
2.
Press push-button [4] (SP) – (LED lights up orange for 3 seconds).
31
] + [CH-2
] + [CH-2
] (VLP) (LED fl ashes red).
] and [Resume] (LED fl ashes red).
9

Technical data

Mains connection
Push-button input
]
DALI interface (data for each channel)
Available DALI control current
Sensor interface
Max. line length
synchronization line / push-button input
Power consumption
Ambient temperature
Type of protection
Protection rating
Conformity
i
Important notes:
Push-button, sensor, and DALI lines must be routed separately from lamp and LED
module supply lines.
If possible, push-button lines should not be routed together with the power supply
in the same cable.
Route sensor lines separately from the power supply.
With longer cable lengths or electromagnetic interference, it is recommended, that
expansion sensors or push-buttons be connected via the DALI line.
To guarantee correct operation of the system new components may only be con-
nected and unclamped / unplugged while in a voltage-free condition.
GB
220 – 240 V AC 50-60 Hz
Floating NO contacts,
(see below under "Important notes")
Max. total cable length: 100 m
Max. 16 EVG + max. 3 DALI
Sensors or push-button couplers
Max. 64 mA on one channel
Max. 96 mA in total via both channels
Max. 4 DALIeco LS/PD LI or
4 DALIeco LS/PD LI NP or
1 HF LS LI Sensor
Max. total cable length
to all sensors: 25 m
50 m (in total)
0.2 W - 3.0 W (depending on
ECG/number of sensors)
-20 °C to +50 °C (operation)
IP20
II, protective insulation
CE

Publicidad

loading