Descargar Imprimir esta página

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

6. Specifications

MODEL
CAPACITY*
INPUT
Low Line Loss
Voltage
Low Line Comeback
EN
Range
High Line Loss
High Line Comeback
Frequency Range
Phase
Power Factor
OUTPUT
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
AC mode
Overload
Battery mode
Current Crest Ratio
Harmonic Distortion
Line
Transfer
Inversor
Time
Inversor
EFFICIENCY
AC mode
Battery Mode
BATTERY
Type & Numbers
Standard
Recharge Time
Model
Charging Current
Charging Voltage
Type
Long-run
Numbers
Model
Charging Current
Charging Voltage
PHYSICAL
Dimension, D X W X H
Standard
Model
Net Weight (kgs)
Long-run
Dimension, D X W X H
Model
Net Weight (kgs)
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude**
Acoustic Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.
6000
Battery
Bypass
ECO
7 hours recover to
90% capacity
1 A ± 10% (max.)
4 A ± 10% (max.)
592X250X576
81
592 X250 X576
25
Less than 55dB @ 1 Meter
Supports Windows®2000/2003/XP/Vista/2008/7, Linux, Unix and MAC
6000R
6000 VA / 4800 W
110 VAC ± 3 % at 50% Load; 176 VAC ± 3 % at 100% Load
Low Line Loss Voltage + 10V
300 VAC ± 3 %
High Line Loss Voltage - 10V
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Single phase with ground
≧ 0.99 at 100% Load
208/220/230/240VAC
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
100%~110%: 10min
110%~130%: 1min
>130% : 1sec
100%~110%: 30sec
110%~130%: 10sec
>130% : 1sec
3:1 max
≦ 3 % @ 100% Linear Load; ≦ 6 % @ 100% Non-linear Load
<10 ms
> 89%
> 88%
12 V / 7 Ah x 20
3 hours recover to
90% capacity
2 A ± 10% (max.)
14.4 V ± 1%
Depending on applications
18 - 20
2 A ± 10% (max.)
14.4 V ± 1%
UPS unit:
580X438X133
Battery pack: 580X438
X133
UPS unit: 17
Battery pack: 57
580 X 438 X 133
17
0 ~ 40°C (the battery life will down when > 25°C)
<95 % and non-condensing
<1000m
Power management from SNMP manager and web browser
29
10000
10000 VA / 8000 W
± 1%
0 ms
0 ms
12 V / 9 Ah x 20
9 hours recover to 90%
4 hours recover to 90%
capacity
1 A ± 10% (max.)
2 A ± 10% (max.)
4 A ± 10% (max.)
2 A ± 10% (max.)
592 X250 X576
Battery pack: 580X438
83
Battery pack: 63
592 X250 X576
668 X 438 X 133
27
Less than 58dB @ 1 Meter
10000R
capacity
UPS unit:
668X438X133
X133
UPS unit: 20
20

Publicidad

loading