Features; Specifications - Macurco RD-12 Instrucciones Para El Usuario

Detector de gas refrigerante, controlador y transductor
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Features

ETL Listed to UL 61010-1 and CAN/CSA C22.2 No 61010-1
Low level meter capable of displaying from 0-1,000 ppm refrigerant gas
Selectable fan and alarm relay activation
5 A SPDT fan relay controls starters of exhaust fans
0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels
4-20 mA Current Loop
RD-12 mounts on a standard 4x4 electrical box and becomes cover for the box
Supervised system: any internal detector problem will cause the fan & alarm relay to activate
Calibration verification test kit is available. One screw allows access for calibration or gas test

Specifications

Power: 100-240VAC (50 TO 60 HZ)
Current: 1.0 A MAX
Shipping Weight: 1 pound (0.45 kg)
Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 10.2 X 5.4 cm)
Color: Dark gray
Connections: plugs/terminals
Mounting box: (not included) 4x4 electric
Fan relay: 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching
Fan relay actuation: selectable at diS (disable), 100 (default), 150, 200, 250, 300, 350ppm
Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
Fan Relay Minimum Runtime settings are 0 (default), 3, 5, 10 or 15 minutes
Fan relay latching or not latching (default) selectable
Alarm relay: 0.5A 120 V, 60 VA
Alarm relay actuation: selectable N.O. (default) or N.C.
Alarm relay settings: diS, 100, 150, 200, 250, 300 (default), 350, 400, 450, 500, 550 or 600ppm
Current Loop: 4-20 mA for 0-1,000 ppm refrigerant gas, selectable to off or on (default)
Buzzer: 85 dBA at 10cm settable to on (default) or off
Digital display: 3 digit LED selectable to on (default) or off
Operating environ: 0°F to 125°F (-18C to 52C).10 to 90% RH non-condensing
Operating altitude: Up to 5,000m (16,404ft)
6

Publicidad

Tabla de contenido
loading

Tabla de contenido