Macurco CD-6G Operation Manual
2.3 Features
•
ETL LISTED to UL 61010-1, Certified to CSA C22.2#61010-1
•
Low level meter capable of displaying from 0-5.0% vol. of CO
•
Sensor Resolution of 0.01% vol.
•
Selectable fan and alarm relay activation
•
5 A SPDT fan relay for control of ventilation systems / communication with Alarm system
•
0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels.
•
4-20 mA Current Loop
•
Mounts on a standard 4x4 electrical box and becomes cover for the box.
•
Supervised system: any internal detector problem will cause the fan & alarm relay to activate.
•
Carbon Dioxide sensor has an expected 15-year life. EOL indicator after 180 months of sensor power-up
•
Calibration verification test kit is available. One screw allows access for gas test.
2.4 Specifications
•
Shipping Weight: 1 pound (0.45 kg)
•
Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 11.4 X 5.3 cm)
•
Color: White or Dark Gray
•
Connections: plugs/terminals
•
Mounting box: (not included) 4x4 electric.
•
Fan relay: 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching
•
Fan relay actuation: selectable at "dIS" (disabled), 0.09, 0.1, 0.11, 0.12, ...0.2(default), ....3.50, 4.0.
•
Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
•
Fan Relay Minimum Runtime settings are 0 (default), 3, 5, 10 or 15 minutes.
•
Fan relay latching or non-latching (default) selectable.
•
Alarm relay: 0.5A 120 V, 60 VA
•
Alarm relay actuation: selectable N.O. (default) or N.C.
•
Alarm relay settings: "dIS" (disabled), 0.09, 0.1, 0.11, 0.12, ...0.5(default), ....3.50, 4.0.
•
Current Loop, 4-20 mA for 0-5.0% vol. CO
•
Buzzer: 85 dBA at 10cm settable to off or on (default)
•
Digital display: 4-digit LED selectable to off or on (default).
•
Operating Environment: 32°F to 122° F (0°C to 50°C), 10 to 90% RH non-condensing
•
Operating altitude: Up to 16,404ft (5,000m)
2.4.1 6-Series Low Voltage
•
Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC
•
Current (max) @ 24 VDC: 126 mA in alarm (two relays), 108 mA (fan relay only) and 85 mA (standby)