Adjusting Air/Gas Pressure Switch - Ecoflam MAX GAS 350 P Manual De Instrucciones

Quemadores de gas de aire soplado
Ocultar thumbs Ver también para MAX GAS 350 P:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 38
420010563501 Max Gas 350 - 500 P/P AB
EN
8,0
7,0
6,0
5,0
4,0
3,0
2,0
1,0
0,0
-1,0
50
100
8,0
7,0
6,0
5,0
4,0
3,0
2,0
1,0
0,0
-1,0
50
100
150
ADJUSTING THE AIR PRESSURE SWITCH
The air pressure switch must be adjusted so that an insufficient air flow does not allow
the CO value to exceed 1% in volume. After having adjusted the gas flow and obtained
optimum combustion (CO
pressure switch must be adjusted. Remove the cover with the burner operating, cover
the air intake progressively with a piece of cardboard to obtain a value of CO
(G20-G25)> 13 (G31) and a CO value of less than 5,000 ppm. Adjust the air pressure
switch until the burner shuts down. Remove the cardboard from the air intake and start
up the burner again. Replace the cover.
ADJUSTING THE GAS PRESSURE SWITCH
Adjust the pressure switch to 50% of the rated pressure of the gas used.
RARED PRESSURE:
PRE-CALIBRATION MAX GAS 500
16
150
200
250
EXAMPLE OF PRE-CALIBRATION MAX GAS 500
16
15
14
13
12,5
1
2
200
250
300
350
400
450
Gas pressure in head
kW
= 9.5 to 9.8% and a CO value of less than 75 ppm), the air
2
G 20 = 20 mbar G 25 = 25 mbar
G 31 = 37 mbar
15
14
13
1
2
300
350
400
kW
Warning: the pre-calibration values have been
determined on EN676 test combustion cham-
bers in ideal conditions, and are useful for the
12
first switch-on but must be checked and correc-
11,5
ted with calibration for the individual system.
Example in figure:
5
Power required by the generator: 380 kW.
4
Pressure envisaged in combustion chamber: 3.5
mbar. Combustion head chamber: 2.5 (between
3
2 and 3). Gas pressure in head: 13 mbar.
500
550
600
pressione gas in testa mbar
Head position
posizione testa
22
12,5
12
11,5
5
4
3
450
500
550
Gas pressure in head
pressione gas in testa mbar
Head position
posizione testa
A
= 10.8
2
B
C
D
600

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Max gas 350 p abMax gas 500 pMax gas 500 p abMax gas 350 pr-mdMax gas 500 pr-md

Tabla de contenido