Communication
Power supply
Current absorbed by BUS
BUS cable
Command elements
Outputs
Max. switchover current
Inputs
Visualisation elements
Measuring elements
Temperature adjustment range
Usage environment
Operating temperature
Storage temperature
Relative humidity
Connection to the BUS
Electric connections
Degree of protection
Size
Standard references
Certifications
TECHNICAL DATA
KNX BUS
Via KNX BUS, 29 V DC SELV + two + 2 1,5AA
alkaline batteries
date and time in the event of a BUS voltage failure.
10 mA
KNX TP1
4 front button keys
1 miniature button key for programming
1 relay with NO/NC potential-free contact
5A (cos =1), 250
1 input for potential-free contact
(max. cable length 10m)
1 input for external temperature sensor
(e.g. GW 10 800) (type NTC 10K)
1 RGB colour display with front light intensity
sensor
1 red LED for programming
1 internal sensor
adjustment range: 5 °C .. +40 °C
measurement range: 0 °C .. +60 °C
measurement resolution: 0,1 °C
measurement accuracy: ±0,5 °C between
+10 °C and +30 °C
T anti-freeze: +2 - +7 °C
T high temperature protection: +30 - +40 °C
Other Setpoints: +5 - +40 °C
Dry, indoor places
-5 - +45 °C
-25 - +70 °C
Max. 93% (non-condensative)
Coupling terminal, 2 pins, Ø 1 mm
Screw terminals - max. cable section: 2,5 mm²
IP20
3 Chorus modules
Low Voltage Directive 2006/95/EC
Electromagnetic Compatibility Directive
2004/108/EC, EN50090-2-2, EN50428
KNX
25
(not included) for maintaining the
V AC
for
adjusting
the
E
N
G
L
I
S
backlighting
H