2b. FIXTURE INSTALLATION
• Insert leads into arm exiting adjacent to pole plate.
• Create a drip loop as shown in Figure 2 For 2" pipe
remove, invert, and refasten the slipfitter clamp.
Loosen clamp to insert arm.
• Slide fixture onto arm to pipe stop. Lightly tighten
slipfitter bolts.
• Level fixture front-to-back using steps and right-to-left
by twisting housing on pipe.
• Tighten clamp bolts to 10-15 foot-pounds
3
WIRING
WARNING
Risk of electrical shock. Make certain power is off before
attempting any maintenance.
NOTE: Verify supply voltage is correct by comparing to
nameplate.
NOTE: Make all electrical connections in accordance
with the National Electrical Code and any applicable
local code requirements including grounding.
3a. ACCESS THE TERMINAL BLOCK (see Figure 4)
• Loosen the captive wiring door screw.
• Grip the door lip, pull down slightly and slide back to remove.
• Reinstall and fasten the wiring door after wiring.
3b. SERVICE LEADS:
• Terminals accept leads from AWG 16 through 6.
• Extend leads about 7" out of mounting arm.
• Refer to Figure 3 and Table 1 for terminal board
connection positions. Attach leads to terminal board
as shown Table 1. Torque the screws per Table 2.
4
MAINTENANCE/CLEANING
• To maintain light output, occasional cleaning of the
outer surfaces may be needed.
• Use a mild, non-abrasive soap or detergent, of neutral
pH (pH 6 to 8) containing no chlorinated or aromatic
hydrocarbons.
• Wash using a soft cloth. Rinse with clean, cold water
and wipe dry.
5
STORAGE
• Packaged units should NOT be stored unprotected
outdoors in corrugated boxes (cardboard boxes).
• Store packaged units in a covered dry area not
exceeding -40°C (-40°F) to 50°C (122°F) such as a
roofed area or covered with a secured tarp to keep
water off the corrugated (cardboard) packaging.
All trademarks are the property of their respective owners. Information provided is subject to
change without notice. All values are design or typical values when measured under laboratory
conditions. Current, powered by GE is a business of the General Electric Company.
© 2017 GE.
www.currentbyge.com
Table 1. Terminal Board Connections
Terminal Board Positions
Table 2. Terminal Torque
Wire Range Copper
10-16
8-6 SOL, STR
Arm
Figure 1.
Figure 2.
Figure 3.
Figure 4.
GEH6063 (Rev 01/09/18) Eng
99003423
Supply Type
L1
High Line
G
N/L2
Line/Neutral
Aluminum
Torque (in. lbs)
STR6, SOL, STR
Thru Bolts
Washer & Nut
Lag Bolts
Pole
Drip Loop
Terminals
Ground
30
45
Wiring Door
Wiring Door Screw
Clamp Bolts
Clamp