STEP 9 . VEHICLE.BATTERY.-.Remove.the.logic.box.cable.grip.nut.for.the.vehicle.battery.and.place.it.on.the.battery.cable.(#10-2.or.
#12-2.depending.on.length).with.the.threads.facing.out . . Thread.the.cable.through.the.cable.grip.until.the.cable.grip.nut.will.grab.the.
cable . . Tighten.the.cable.grip.nut.and.attach.the.individual.wires.to.the.proper.terminals.(see.wiring.schematic.Figure.6) . . Reattach.the.
logic.box.cover.and.secure.with.the.6.screws .
.
.
.
NOTE:..To.supply.enough.current.to.operate.the.monitor.properly,.adequate.wire.size.is.critical .
OPERATING INSTRUCTIONS
A . . CONTROLLER.OPERATION
The.controller.is.used.to.control.the.monitor.and.nozzle .
1 . . ..
To.deploy.the.monitor.for.use:..
.
Lift.the.safety.cover.on.the.STOW/DEPLOY.switch.and.push.the.toggle.switch.up.and.release . .
.
Note:.Some.models.may.not.be.equipped.with.a.deploy.switch . . The.Deploy.Function.will.only.lower.the.monitor . . . .
.
See.DIP.Switch.3.and.4 .
2 . . ..
To.stow.the.monitor.after.use:
.
Lift.the.safety.cover.on.the.STOW/DEPLOY.switch.and.push.the.toggle.switch.down.and.release . . Note:.Some..
.
.models.may.not.be.equipped.with.a.deploy.switch . .
3 . . ..
To.change.the.horizontal.monitor.position.toward.the.right.or.left:.
.
Press.the.proper.toggle.switch.toward."RIGHT".or.."LEFT".respectively,.as.labeled.on.the.controller,.until.the..
.
desired.position.is.reached .
4 . . ..
To.change.the.vertical.monitor.nozzle.position.upward.or.downward:.
.
Press.the.proper.toggle.switch.toward."RAISE".or."LOWER".respectively,.as.labeled.on.the.controller,.until.the..
.
desired.position.is.reached .
5 . . ..
To.change.the.nozzle.pattern.toward.the.straight.stream.or.fog.position:.
.
Press.the.proper.toggle.switch.toward."STRAIGHT".or."FOG".respectively,.as.labeled.on.the.controller,.until.the..
.
desired.nozzle.position.is.reached .
THE.LOWER.CONTROL.BOX.FUNCTIONS.WILL.OVERRIDE.THE.UPPER.CONTROL.BOX.FUNCTIONS.IN.
COMPLIANCE.WITH.THE.REQUIREMENTS.OF.THE.NFPA.STANDARD . . NOTE:.THE.LOWER.CONTROL.AND.UPPER.CONTROL.WIRES.
MUST.BE.ATTACHED.TO.THE.CORRECT.TERMINALS.FOR.THE.LOWER.CONTROL.(MASTER).TO.OVERRIDE.THE.UPPER.CONTROL.
(SLAVE) . . NONE.OF.THE.FUNCTIONS.CAN.BE.CONTROLLED.FROM.THE.UPPER.CONTROL.BOX.WHEN.ANY.OF.THE.SWITCHES.ON.
THE.LOWER.CONTROL.BOX.ARE.ACTIVATED .
B . . EMERGENCY.STOP.DURING.DEPLOY.OR.STOW
.
. I f.it.is.necessary.to.immediately.stop.the.StreamMaster.monitor.during.the.deploy.or.stow.sequence,.activate.any.switch.on.
the.control.panel.and.the.unit.will.stop.moving.(E-Stop) . . .To.continue.operation.after.an.emergency.stop,.operate.any.switch.
or.press.the.Stow.or.Deploy.switch.to.continue.the.sequence .
C . . MANUAL.OVERRIDE.CONTROLS
.
. T he.manual.override.control.is.to.be.used.only.when.the.power.to.the.monitor.is.off . . .A.override.attached.to.the..
monitor.for.use.on.both.the.horizontal.and.vertical.override.controls . . .
.
NOTE:.Some.models.have.permenently.attached.override.handwheels.instead.of.a.crank .
WARNING:
The override handwheel will turn during normal operation of the monitor. Keep clear of the
override handwheel to prevent entanglement.
D . . THE.ROTATION.AND.ELEVATION.LIMITS
The.hard.limits.are.factory.set.at.180°.Rotation,.and.SETUP:.-45°.to.+45°.Elevation.with.physical.stops .
The.soft.limits.are.not.set.at.the.factory . . .To.change.the.soft.limits:
.
•.Shut.down.power.to.the.monitor
.
•.Hold.down.the.SS.switch.and.turn.the.power.on . . .Release.the.SS.switch
Page.5
.
.
.
.