Emerson FloBoss 107 Instrucciones Para Un Uso Seguro página 6

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 45
Safe Use Instructions – Emerson FloBoss 107 Flow Manager
Part D301594X012
February 2018
DANGER
Do not over torque the connector screws.
Note: Check the input power polarity before
turning on the power.
7. Apply power to the FB107.
8. Configure the FB107 before you place it into service.
You configure the device using ROCLINK 800
Configuration software, which runs on a personal
computer. You normally connect the PC to the
FB107's LOI port to transfer configuration data into
the FB107, although you can also develop
configurations off-line and later load them into the
FB107.
The FB107 firmware provides default values for all
parameters. If the default values are acceptable for
your application, leave them as found. You use
ROCLINK 800 to adjust parameter values. Refer to the
ROCLINK 800 Configuration Software User Manual (for
FloBoss 107) (part D301249X012).
9. The calibration routines support 5-point calibration,
with the three mid-points calibrated in any order. The
low-end or zero reading is calibrated first, followed by
the high-end or full-scale reading. The three mid-
points can be calibrated next, if desired. The
diagnostic analog inputs—logic voltage (E1), battery
voltage (E2), and board/battery temperature (E5)—are
not designed to be calibrated.
With the optional I/O termination points installed,
calibrate the Analog Input using ROCLINK 800.
4
The calibration procedure for these analog inputs is
described in the ROCLINK 800 Configuration Software
User Manual (for FloBoss 107) (part D301249X012).
10. To troubleshoot problems with the FB107, identify
whether the problem is with the configuration or the
hardware. Verify (using ROCLINK 800) the
configuration to identify any incorrect settings.
Inspect the hardware for damage. Inspect the
termination boards for connection location errors.
If the problems with the FB107 appear to be software
related, try resetting the FB107 with a warm start,
cold start, or reset.
Note: Resetting the firmware may restore the device
and its configuration to factory settings.
Ensure that you have saved any configuration
settings to your PC or some removable media.
If you are experiencing problems that appear to be
hardware-related, verify the wiring. If you still
experience problems, contact your local sales office
for return authorization.
11. To remove the FB107 from service:
Verify safe area.
Disconnect power from the unit.
Remove all external wiring connections.
Remove the FB107 from its enclosure.
12. Place the FB107 in a suitable container for
transportation or shipment.