EJB, Style C Model M82 Series
Junction Boxes
Installation & Maintenance Information
APPLICATION
EJB series junction boxes are used as a junction box or pull box in rigid
conduit systems.
EJB series junction boxes are suitable for use indoors or outdoors and
are UL Listed and CSA Certified for Class I, Groups B, C, D; Class II,
Groups E, F, G; and Class III hazardous (classified) areas as defined by
®
the National Electrical Code
include a gasket to meet Type 4 watertight requirements.
INSTALLATION
WARNING
1. Electrical power must be off before and during
installation and maintenance.
2. Field modification of this product is not permitted.
1. EJB series junction boxes are furnished with or without drilled
and tapped openings. Drilling and tapping of conduit
openings is subject to the limitations of maximum size and
*Body and Cover
® National Electrical Code is a Register Trademark of the National Fire Protection Association.
® Canadian Electrical Code is a voluntary code for Adoption and Enforcement by Regulatory Authorities.
IF 931 • 08/08
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
and the Canadian Electrical Code
Figure 1. EJB-M82 Dimensions
Copyright © 2008, Cooper Industries, Inc.
EJB series classified enclosures ordered with suffix -ATEX meet the
ATEX directive and are certified by ETL. EJB classified enclosures with
-ATEX suffix have the following classification: (
ATEX certified boxes have an IP 66 rating. ATEX suffix junction box
complies with EN60079-0:2006 and EN60079-1:2006 Certificate ITSØ8
ATEX 15797U. ATEX certified boxes cannot be field drilled and tapped
for entries. All entries must be drilled and tapped by Cooper Crouse-
Hinds at the factory.
®
, and
EJB series junction boxes should be installed, inspected and maintained
by qualified and competent personnel.
number of openings as well as spacings. Refer to DRILLING
AND TAPPING section following. All machining must be
done prior to installation.
2. Select a mounting location that will provide suitable strength
and rigidity for supporting all contained wiring and control
devices. Figure 1 shows the mounting dimensions for the
four detachable mounting feet.
IF 931
) II 2 G Ex d IIB + H2.
IMPORTANT
ATEX certified boxes MAY NOT
be field drilled and tapped.
Entries must be machined by
factory.
Page 1

Publicidad

loading

Resumen de contenidos para Cooper CROUSE-HINDS EJB Serie

  • Página 1 ATEX 15797U. ATEX certified boxes cannot be field drilled and tapped EJB series junction boxes are suitable for use indoors or outdoors and for entries. All entries must be drilled and tapped by Cooper Crouse- are UL Listed and CSA Certified for Class I, Groups B, C, D; Class II, Hinds at the factory.
  • Página 2 Make sure all cover bolts are fully (class and group) in which they are being installed. retracted into the cover before attempting to open or close the cover. IF 931 • 08/08 Copyright © 2008, Cooper Industries, Inc. Page 2...
  • Página 3 5” or 3 1/2” entries. ‡ These instructions can be used for Group B locations, provided no entry machined in the wall of the enclosure exceeds 4” trade size. IF 931 • 08/08 Copyright © 2008, Cooper Industries, Inc. Page 3...
  • Página 4 • The approval applies to equipment without cable glands. When mounting Cooper Crouse-Hinds recommends an Electrical Preventative Maintenance the flameproof enclosure in a hazardous area, only rigid metal conduit Program as described in the National Fire Protection Association Bulletin NFPA 70B.
  • Página 5 ® National Electrical Code est une marque déposée de National Fire Protection Association. Le ® Canadian Electrical Code (Code électrique canadien) est un code volontaire pour l’adoption et l’application par les autorités réglementaires. IF 931 • 08/08 Copyright © 2008, Cooper Industries, Inc. Page 5...
  • Página 6 9. Si les boulons du couvercle sont endommagés, veuillez remplacer puis retirez le couvercle et placez-le de côté afin d’éviter d’endommager uniquement avec des boulons de Cooper Crouse-Hinds. Pour déterminer les joints rodés et les joints de bride. les pièces de rechange appropriées, veuillez consulter le tableau ci- dessous : REMARQUE : Les boîtes à...
  • Página 7 5 po sont permises sur un côté.‡ Par exemple, une quantité de quatre (Les boîtes certifiées ATEX doivent contenir des entrées (4) entrées de conduit de 5 po est permise sur le long côté d’un modèle percées et taraudées machinées à l’usine de Cooper Crouse- EJB361808. Hinds) 2.
  • Página 8 • L’approbation s’applique à l’équipement sans les presse-étoupe. Lors du Cooper Crouse-Hinds recommande un programme d’entretien électrique montage de la boîte antidéflagrante dans un secteur dangereux, seuls les systèmes de conduit en métal rigide ou les presses-étoupe préventif comme décrit dans le bulletin national NFPA 70B de l’association de...
  • Página 9: Cajas De Conexiones De La Serie Ejb, Estilo C, Modelo M82

    Todas las entradas deben ser perforadas y áreas peligrosas (clasificadas) Clase I, Grupos B, C, D; Clase II, roscadas por Cooper Crouse-Hinds en la fábrica. Grupos E, F, G; y Clase III según las definiciones del National Electrical ®...
  • Página 10 9. En caso de dañarse los pernos de la tapa, reemplácelos exclusivamente con pernos suministrados por Cooper Crouse-Hinds. NOTA: Las cajas de conexiones EJB sin bisagras en la tapa tienen...
  • Página 11 ‡ Estas instrucciones pueden usarse para ubicaciones del Grupo B, siempre y cuando ninguna entrada hecha en la pared del gabinete sea superior a un tamaño comercial de 4”. IF 931 • 08/08 Copyright © 2008, Cooper Industries, Inc. Página 11...
  • Página 12: Mantenimiento

    La aprobación se aplica a equipos sin prensacables. Al montar el gabinete ignífugo en un área peligrosa, se deben utilizar únicamente Cooper Crouse-Hinds recomienda un Programa de Mantenimiento Eléctrico sistemas de conductos de metal rígidos o prensacables ignífugos con Preventivo como el que se describe en el boletín NFPA 70B de la Asociación certificación EN60079.