Champ LED Floodlight
FMVA20L/FMVA25L LED Luminaires
Installation & Maintenance Information
APPLICATION
Champ
LED floodlights are suitable for use in the following hazardous (classified)
®
locations as defined by the National Electrical Code (NEC
FMV:
NEC/CEC:
• Class I, Division 2, Groups A, B, C, D
• Class I, Zone 2
• Class II, Groups E, F, G
• Wet Locations, Type 4X, IP66
UL Standards:
• UL844 Hazardous (Classified), UL1598 Luminaires, UL1598A Marine, UL8750
• CSA 22.2 No. 250.0-08
To avoid the risk of fire, explosion or electric shock, this product should be
installed, inspected and maintained by a qualified electrician only, in accordance
with all applicable electrical codes.
To avoid electric shock:
•
Be certain electrical power is OFF before and during installation and
maintenance.
To avoid burning hands:
•
Make sure LEDs and drivers are cool to touch when performing
maintenance.
INSTALLATION
Mounting
Yoke Mount - Wall Mount Using Floodlight Yoke Only
1.
Using floodlight yoke as a template, mark and drill desired location on mounting
surface.
2.
Secure floodlight yoke to surface using ½" bolts or lag screws (not provided).
WIRING
Wiring the Floodlight
1.
Open back cover/heat sink by loosening nine (9) #10-24 x 0.75" stainless steel
cover screws using a 5/16" nut socket or flat head screwdriver (see Figure 1).
The heat sink cover should be removed by pulling back on one corner of the top
most edge to prevent damage to gasket.
NOTE: To avoid pinching hazard between heat sink cover and driver housing, ensure
that floodlight is oriented in vertical position before, and during, wiring procedure.
2.
All components in the fixture are pre-wired so only line in, neutral and ground
need to be connected in the fixture using the supplied Wago connectors, using
methods that comply with all applicable codes. See Figure 2 for wiring diagram.
•
Wire range from AWG 20-14 (strip length 0.43").
•
Entries to driver housing shall have thread lubricant HTL or STL applied,
following NEC guidelines, and all applicable local codes.
•
Standard openings are 3/4" NPT.
•
Optional openings are M20 (20mm) and/or M25 (25mm).
•
Secure all electrical connections and wiring entry glands.
•
Ensure that the following lengths for field wiring, internal to the driver
housing compartment, are followed:
– 4.5" ± 0.25" (114 ± 6mm) for ground wire
– 2.5" ± 0.25" (64 ± 6mm) for neutral wire
– 2" ± 0.25" (51 ± 6mm) for line in wire
LINE TERMINAL
IF 1828 • 02/19
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
):
®
WARNING
WARNING
NEUTRAL TERMINAL
Copyright
Refer to the floodlight nameplate for specific classification information, maximum
ambient temperature suitability and corresponding operating temperature (T-code).
Champ LED floodlights' construction is designed for use indoors and outdoors in
marine and wet locations, where moisture, dirt, corrosion, vibration and rough usage
may be present.
Champ LED floodlights are supplied for use with a choice of voltages:
• 100-277 VAC, 50/60 Hz
• 127-300 VDC
• 347-480 VAC, 50/60 Hz
Champ LED floodlights are compliant with the regulation on the assessment of
product compliance for explosive atmospheres.
To avoid explosion:
•
Make sure the supply voltage is the same as the rated floodlight voltage.
•
Do not install where the marked operating temperatures exceed the
ignition temperature of the hazardous atmosphere.
•
Do not operate in ambient temperatures above those indicated on the
floodlight nameplate.
•
Use only replacement parts from Eaton's Crouse-Hinds Division.
•
Use proper supply wiring as specified on the floodlight nameplate.
•
All surfaces must be clean.
•
LED compartment non-serviceable. Do not open.
•
Before opening wiring compartment, electrical power to the floodlight
must be turned off and area must be free from hazardous atmosphere.
Keep tightly closed when in operation.
Cover/heat sink
GROUND TERMINAL
2019, Eaton's Crouse-Hinds Division
®
WARNING
COVER SCREWS
Figure 1
IF 1828
DO NOT PLACE
ADDITIONAL
WEIGHT ON THE
BACK COVER/
HEAT SINK
Page 1