Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

Champ LED floodlight FMVA LED fixtures Gen. II - UNV1
Installation & maintenance information
APPLICATION
Champ
LED floodlights are suitable for use in the following hazardous (classified)
®
locations as defined by the National Electrical Code (NEC
FMV:
NEC/CEC:
• Class I, Division 2, Groups A, B, C, D
• Class I, Zone 2
• Class II, Groups E, F, G
• Wet Location, Type 4X, IP66
IECEx & ATEX:
• IECEx UL15.0029X
• DEMKO 15 ATEX 1377X
• DEMKO 15 ATEX 1383
• Ex II 3 G Ex ec mb IIC T5 Gc Tamb -40° - +40°C*
• Ex II 3 G Ex ec mb IIC T4 Gc Tamb -40° - +55°C
• Ex ec mb IIC T5 Gc Tamb -40°C - +40°C*
• Ex ec mb IIC T4 Gc Tamb -40°C - +55°C
• Ex II 2 D Ex tb IIIC T65 Db Tamb -40°C - +40°C
• Ex II 2 D Ex tb IIIC T80 Db Tamb -40°C - +55°C
• Ex tb IIIC T65 Db Tamb -40°C - +40°C
• Ex tb IIIC T80 Db Tamb -40°C - +55°C
0539
*T4 when used with 3x3 optic.
To avoid the risk of fire, explosion or electric shock, this product should be
installed, inspected and maintained by a qualified electrician only, in accordance
with all applicable electrical codes.
To avoid electric shock:
Be certain electrical power is OFF before and during installation and
maintenance.
Floodlight must be supplied by a wiring system suitable per local code with
an equipment grounding conductor.
To avoid burning hands:
Make sure LEDs and drivers are cool to touch when performing
maintenance.
INSTALLATION
Mounting
Yoke Mount - Wall Mount Using Floodlight Yoke Only
1.
Using floodlight yoke as a template, mark and drill desired location on mounting
surface.
2.
Secure floodlight yoke to surface using ½" bolts or lag screws (not provided).
WIRING
Wiring the Floodlight
1.
Open back cover/heat sink by loosening nine (9) #10-24 x 0.75" stainless steel
cover bolts using a 5/8" nut socket or flat head screwdriver (see Figure 1). The
heat sink cover should be removed by pulling back on one corner of the top
most edge to prevent damage to gasket.
NOTE: To avoid pinching hazard between the heat sink cover and driver housing,
ensure that the floodlight is oriented in the vertical position before, and during wiring
procedure.
DO NOT PLACE ADDITIONAL WEIGHT ON THE BACK COVER/HEAT SINK
IF 1883 • 08/19
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
):
®
WARNING
WARNING
Figure 1
Copyright
UL standards:
• UL 844 Hazardous (Classified), UL1598 Luminaires, UL1598A Marine, UL8750
IEC standards:
• IEC 60079-0, 6
th
(2013-11) + I-SH 02 (2014-10)/EN 60079-0:2012 + A11:2013
• IEC 60079-7, Edition 5.1 (2017-08)/EN 60079-7: 2015 +A1:2018
• IEC 60079-18, Ed. 4.1 (2017-08) + Corr. 1 (2018-07)/EN 60079-18:2015 + A1:2017
• IEC 60079-31, 2
• IEC 60598-1:2008/EN60598-1:2008
• IEC 60598-2:2008/EN60598-2:2008
Refer to the floodlight nameplate for specific classification information, maximum
ambient temperature suitability and corresponding operating temperature (T-code).
Champ LED floodlights' construction is designed for use indoors and outdoors in
marine and wet locations, where moisture, dirt, corrosion, vibration and rough usage
may be present.
Champ LED floodlight voltage ranges for VAC/VDC:
• IECEx/ATEX – 100-240 VAC, 50/60Hz
• US/CAN – 100-277 VAC/50/60 HZ
• US/CAN/ATEX/IECEx – 127-250 VDC
Champ LED floodlights are compliant with the regulation on the assessment of
product compliance for explosive atmospheres.
To avoid explosion:
Make sure the supply voltage is the same as the rated floodlight voltage.
Do not install where the marked operating temperatures exceed the
ignition temperature of the hazardous atmosphere.
Do not operate in ambient temperatures above those indicated on the
floodlight nameplate.
Use only replacement parts from Crouse-Hinds.
Use proper supply wiring as specified on the floodlight nameplate.
All surfaces must be clean.
Before opening, electrical power to the floodlight must be turned off and
area must be free from hazardous atmosphere. Keep tightly closed when
in operation.
To minimize the risk from electrostatic discharge, when cleaning, wipe the
lens with a clean, damp cloth.
2.
All components in the fixture are pre-wired so only line in, neutral and ground
need to be connected in the fixture using the terminal block, using methods
that comply with all applicable codes. Insert wires into terminal block by
pressing down on tabs. Be sure wires are spaced as shown in Figure 2.
Wire range from AWG 18-14 (0.75 - 2.5mm²) for neutral, and line (strip
length 0.43" [10.9mm]), and AWG 16-14 (1.5 - 2.5mm²) for ground
connections (strip length 0.43" [10.9mm]).
Entries to driver housing shall be sealed, using HTL or STL, with devices
rated a minimum of IP66.
Standard openings are M20, M25 or 3/4" NPT.
Optional openings are M20 (20mm) and/or M25 (25mm).
Secure all electrical connections and wiring entry glands.
Ensure that the following lengths for field wiring, internal to the driver
housing compartment, are followed:
– 4.5" ± 0.25" (114 ± 6mm) for ground wire
– 2.5" ± 0.25" (64 ± 6mm) for neutral wire
– 2" ± 0.25" (51 ± 6mm) for line in wire
2019, Eaton's Crouse-Hinds Division
®
Edition (2011-06) + Corr. 1 (2012-01) + Corr. 2 (2013-12) + I-SH 01
Edition (2013-11)/EN 60079-31:2014
nd
WARNING
LINE TERMINAL
Figure 2
IF 1883
NEUTRAL TERMINAL
GROUND TERMINAL
Page 1

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Eaton CROUSE-HINDS Champ FMVA Serie

  • Página 1 DO NOT PLACE ADDITIONAL WEIGHT ON THE BACK COVER/HEAT SINK LINE TERMINAL NEUTRAL TERMINAL GROUND TERMINAL Figure 1 Figure 2 IF 1883 • 08/19 Copyright 2019, Eaton’s Crouse-Hinds Division Page 1 ®...
  • Página 2: Wiring Diagram

    Collinite NCF or Duco #7. Do not use an • FMVA 15L UNV1 DRIVER KIT - covers FMVA/PFMA 15L UNV1 fixtures IF 1883 • 08/19 Copyright 2019, Eaton’s Crouse-Hinds Division Page 2 ®...
  • Página 3 Hinds “Terms and Conditions of Sale,” and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith. Eaton’s Crouse-Hinds Division IF 1883 1201 Wolf Street, Syracuse, New York 13208 •...
  • Página 4: Instalación

    – 2" ± 0,25" (51 ± 6 mm) para cable en línea NO COLOQUE PESO ADICIONAL EN LA CUBIERTA POSTERIOR O EL DISIPADOR DE CALOR LINE TERMINAL NEUTRAL TERMINAL GROUND TERMINAL Figura 1 Figura 2 IF 1883 • 08/19 Derechos de autor 2019, Eaton’s Crouse-Hinds Division Página 1 ®...
  • Página 5: Diagrama De Cableado

    No utilice limpiadores alcalinos fuertes y abrasivos o limpiadores ácidos. Esto puede dispositivos UNV1 provocar daños. • KIT DE ACCIONADOR FMVA 15L UNV1 - cubiertas FMVA/PFMA 15L, dispositivos UNV1 IF 1883 • 08/19 Derechos de autor 2019, Eaton’s Crouse-Hinds Division Página 2 ®...
  • Página 6 En conformidad con los “Términos y condiciones de venta” de Crouse-Hinds y dado que las condiciones de uso están fuera de nuestro control, el comprador debe determinar la idoneidad del producto para su uso previsto y asume todos los riesgos y responsabilidades en relación con este. Eaton’s Crouse-Hinds Division IF 1883 1201 Wolf Street, Syracuse, New York 13208 •...
  • Página 7 – 51 mm ± 6 mm (2 po ± 0,25 po) pour le fil de phase et ce, avant et pendant le câblage. NE PAS PLACER DE POIDS SUPPLÉMENTAIRE SUR LE COUVERCLE ARRIÈRE/LE DISSIPATEUR DE CHALEUR LINE TERMINAL NEUTRAL TERMINAL GROUND TERMINAL Figure 1 Figure 2 IF 1883 • 08/19 © Division Crouse-Hinds d’Eaton, 2019 Page 1...
  • Página 8: Schéma De Câblage

    • TROUSSE DE CIRCUIT pour la série FMVA UNV1 de 15L – convient aux luminaires 15L ou Duco no 7. Ne pas utiliser d’abrasif ni de nettoyant fortement alcalin ou acide car des de série FMVA/PFMA UNV1 dommages peuvent être causés. IF 1883 • 08/19  Division Crouse-Hinds d’Eaton, 2019 Page 2 ©...
  • Página 9 Conformément aux conditions de vente de Crouse-Hinds, et étant donné que les conditions d’utilisation sont indépendantes de notre volonté, l’acheteur doit déterminer si le produit convient à l’utilisation prévue et en assume tous les risques et toutes les responsabilités associées. Division Crouse-Hinds d’Eaton IF 1883 1201 Wolf Street, Syracuse, New York 13208 •...

Tabla de contenido