I-40 Manual and Spark Ignition
11. The heaters require a regulated gas supply to the
gas inlet. Exceeding the gas inlet pressure rating
can result in poor performance and unreliable oper-
ation. Refer to page 4 of this manual for information
on gas pressures relating to specifi c models.
12. The heater is designed for butane / propane gas.
Do not use this heater in an LPG liquid withdrawal
system. Do not permit LPG in liquid form to enter
the heater at any time.
13. The corrosive atmosphere present in animal
confi nement buildings can cause component
failure or heater malfunction. The heater should be
periodically inspected and cleaned in accordance
with the Maintenance and Cleaning Instructions in
this manual. Make sure that livestock is protected
by a back up alarm system that limits high and low
temperatures and also activates appropriate alarms.
14. Take time to understand how to operate and main-
tain the heater using the owner's manual. Make
sure you know how to shut off the gas supply to the
building and to the individual heaters. Contact your
gas supplier if you have any questions.
15. Any defects found in performing any of the service
procedures must be eliminated and defective parts
replaced immediately. Retest the heater before
placing it back into service.
Owner's Manual • I-40