Self-Diagnosis Function; Dip Switch Setting - Friedrich DUCTLESS Manual De Instalación

Ocultar thumbs Ver también para DUCTLESS:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

28

SELF-DIAGNOSIS FUNCTION

Indoor Unit Error
Ex) Error 03 (Remote controller error)
3 Times
LED02G
(GREEN)
Error Code
01
Indoor Room sensor error
02
Indoor in-pipe sensor error
03
Remote controller error
04
Drain pump error
05
Communication error indoor and outdoor
06
Indoor out-pipe sensor error
09
EEPROM error (indoor)
10
BLDC motor fan lock (indoor)
h Because remote controller turn off when occur ERROR in simultaneous operation system, it
should check LED blinks of outdoor in order to confirm error code.
h Repeatedly after LED1 is turned on and off as the Error code number of tens digit, LED2 is
turned on and off as the Error code number of single-digit.

DIP SWITCH SETTING

Function
SW3 Group Control
Dry Contact
SW4
Mode
SW5
Installation
3 Times
2 Sec.
2 Sec.
Description
Description
Selection of Master or
Slave
Selection of Dry Contact
Mode
Fan continuous operation
3 Times
LED 1(Red) LED 2(Green)
1time ◑
Setting Off
Master
Wired/Wireless remote
controller
Selection of Manual or
Auto operation Mode
Continuous operation
Removal
1time ◑
0
2times ◑
0
3times ◑
0
4times ◑
0
5times ◑
0
6times ◑
0
9times ◑
0
Indoor PCB
0
Indoor PCB
Indoor PCB
Indoor PCB
Setting On Default
Slave
Auto
Working
Indoor
status
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Off
Off
Off

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido