Initial Operation - Eaton SURE-LITES EUX Instrucciones De Instalación

Batería de respaldo con autodiagnóstico
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation Instructions for the EUX Universal Edge Lit Exit –
Battery Backup with Self Diagnostics
Usage Instructions for the Sure-Lites Eagle Eye Self
Diagnostics
The Sure-Lites Eagle Eye Self Diagnostics is continuously
monitoring your emergency fixture, and will signal any
failure through the 3 color indicator LED.

Initial Operation:

When the unit is first powered up, it will go into a 24
hour fast charge, indicated by the indicator LED pulsing
green. Once the unit has fully charged, it will perform a
self calibration, after which the LED will change to steady
green, indicating the unit is fully charged and float
charging the battery to maintain readiness.
Automatic Testing:
The unit will perform a battery capacity, lamp/LED, and
charge circuit test every 30 days for 30 seconds. During
this time, the indicator LED will change to a steady
yellow. It will perform a full battery capacity (90 minute)
test once per year. During this time, the indicator LED
will change to a blinking yellow.
Manual Testing
• 10 Second "Installation" test – Press and release the
test button once during fast charge (blinking green) to
initiate a 10 second quick test. The sign will switch to
emergency mode for 10 seconds allowing the installer
to verify proper installation of the unit, and the LED
indicator will turn solid yellow.
• 30 Second Test - Press and release the test button
once during float charge (steady green). The indicator
LED will turn steady yellow to indicate the unit is
performing a 30 second test of the batteries and lamps/
LEDs.
• 90 Minute Test - Press and release the test button a
second time during a 30 second test (steady yellow) to
change to a 90 minute test. During this test, the LED
indicator will change to blinking yellow, and the circuit
will perform a full battery capacity, charge circuit, and
LED test.
• Canceling Test – Press and release the test button
during the 90 minute test (flashing yellow) to return the
fixture to its original state (fast charge or float charge)\
Sure-Lites
4
OFF-Emergency
Mode/Power Off
Steady Blink Green -
Fast Charge
Steady Green -
Full/Float Charge
Steady Yellow -
Quick Test
Installation Instructions for the EUX Universal Edge Lit Exit – Battery Backup with Self Diagnostics
Laser Test
The EUX is equipped with a Laser Test function, that
allows the unit to be manually tested without the need to
physically press the test button. Shining a laser pointer
in the hole marked "LASER TEST" on the bottom of the
unit has the same effect as a press and release of the test
button.
Clearing Failure Codes
• A battery failure (LED two blink red) can be cleared by
replacing the battery. Disconnecting the battery and
AC power, or performing a full 90 minute discharge,
will reset the error code, however, it will return if the
battery is faulty.
• Charge Circuit (LED three blink red) and lamp/LED
failure will clear when the unit successfully passes a
manual or automatic 30 second test.
Indicators:
• LED Off - No power to unit, emergency mode.
• LED Steady Green - Unit is fully charged and is float
charging the battery to maintain readiness.
• LED Green Pulse - Unit is in a 24 hour fast charge of the
battery.
• LED Two Blink Red - Battery has failed a capacity test,
or the battery is disconnected. See "Clearing Failure
Codes" above.
• LED Three Blink Red - Battery charge circuit has failed.
See "Clearing Failure Codes" above.
• LED Four Blink Red - Lamps have burned out, or on an
EXIT/Combo, 50% or more of the LEDs have failed. See
"Clearing Failure Codes" above.
• LED Steady Yellow - 30 second test or 10 second quick
test (Fast Charge only).
• LED Blinking Yellow - 90 minute test.
049-241
ADX141174
www.eaton.com
Steady Blink Yellow -
90 Minute Test
2 Blink Red -
Battery Failure
3 Blink Red -
Charge Circuit Failure
4 Blink Red -
Lamp/LED Failure