9. Checking Signal Strenght :
– make sure that at least one of the green LEDs remains lit; all green LEDs lit indicates perfect coverage;
– if the green LEDs are not illuminated, the signal strength is TOO WEAK; change the position of the antenna until you
find a position which offers acceptable signal strength.
10. Close the control panel cover.
, , , , , Connect power circuit only after the cabinet has been secured to the building or structure and has been
connected to the protective earth ground of the building.
! ! ! ! !
Before inserting or removing the SIM card, please ensure the unit is powered down.
This section describes the various terminals. Figure 4 shows a typical wiring diagram.
+V (1) Power supplied by the control unit or by the external power supply (optional), at a level between 9.6 and
27.6V dc, make sure that this is protected and operating at a limited current; Limited power source (LPS) in
conformity with EN 60950-1:2006 standard.
! ! ! ! !
To connect the supply use wires with a maximum 2 mt length and 0.75mm² cross-section. For shorter
wires use suitable cross-sections.
M
M
M
M
M (2) Negative power supply and shared teminal for the Open Collector outputs.
T1 (3), T2 (4) Open Collector outputs: these outputs are activated by breakdown events on the PSTN line or on the GSM network.
T3 (5) Programmable Open Collector output: this output may be activated by a caller identification event. The maximum
current sink of each OC Output must not exceed 100 mA.
-
-
-
- (6) Earth Ground: This terminal must be connected to the Mains Earth, in order to comply with the Telecommunications
-
Network Safety Standards (Overvoltage Protection Requirements).
LE (7-8) External telephone line: These terminals can be connected to the land line.
L I (9-10) Internal telephone line: These terminals must be connected to the control panel or an alternative communication
terminal.
! ! ! ! ! The Open Collector current may not exceed 100 mA. If necessary, commutate greater loads using switches.
,
Fig. 3 - Fitting the antenna with metal bracket or the ANT-EU antenna.