Festo CTEU-DN Manual Del Usaurio página 4

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 5
Bus node, type CTEU-DN
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.Set the baud rate: When setting the baud rate, take into
account the length of the network lines (main bus line,
branch lines and branches)
see subsequent note.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maximum effective data rate (baud rate)
The setting of the baud rate depends on the length of
all network lines.
• Consider the length of the fieldbus line between the
PLC and bus node (main bus line) as well as the
length of possibly available branch lines and
branches (for continued fieldbus configuration).
• Also consider the overall length (sum) of all branch
lines.
• The subsequent table supplies reference values for
the maximum baud rate, dependent on the line
lengths.
The baud rates named here are not supported by all
controllers.
• Observe possibly deviating specifications in the
manual of your control system or network scanner.
Further information can be found in the specifica-
tions of the ODVA
www.odva.org.
Max. data rate (baud rate)
dependent on the line length (reference values)
2)
Main bus
Branch line
Baud rate
1)
line
Individual
All branch lines
branch line
(sum)
Max. 100 m
Max. 6 m
Max. 39 m
500 kBaud
Max. 250 m
Max. 6 m
Max. 78 m
250 kBaud
Max. 500 m
Max. 6 m
Max. 156 m
125 kBaud
1)
Trunk line
2)
Drop line
3.Set the diagnostics and fail-state mode.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Functional test:
– The LED MNS flashes green or is lit green
(if configured via the network, i.e. in case of correct
communication with the PLC
chap. 6).
– Die LED IO is off, flashes green or is lit green
(if configures via the network).
5.3 Mounting of the DIL switch cover
1.Place the cover carefully on the bus node. Make sure
that the seal is seated correctly!
2.Tighten the two mounting screws at first hand-tight and
then with max. torque 0.4 Nm.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 Status display/diagnostics via LEDs
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
You will find additional information on the LEDs as well
as on diagnostics and error elimination in the descrip-
Note
tion "Universal bus node CTEU-DN – function and
maintenance" in the Internet under
Support portal
User documentation.
PS – Status of operating voltage supply
(power system)
LED
Status and significance
display
LED illuminated green:
– Normal operating status
– Operating voltage applied (in the approved range)
– Load voltage present (in the approved range)
LED flashes green (flashing frequency: 1 Hz)
– Operating voltage is below the required voltage
– Load voltage is below the required voltage
1)
– Short circuit at the I-port
LED is off:
– Operating voltage not applied
1)
Display depends on whether the connected device monitors the
load voltage and reports to the bus node
1)
X1 or X2
– Internal communication between bus node
1)
and device 1 or 2
LED
Status and significance
display
LED illuminated green:
– Normal operating status
– Device is correctly connected to the bus node
– Operating and load voltage present
2)
(in the approved range)
LED flashes green:
– Connected device reports diagnostics status
– Undervoltage at system or additional power supply
– Connection between bus node and device is OK
LED illuminated red:
– Device is connected correctly to the bus node,
but internal communication is faulty
– After commissioning, incorrect device connected
Note
(non-I-port-compatible device recognised)
– Device was removed after initialization of the bus
node
LED flashes red:
– During commissioning, incorrect device connected
(non-I-port-compatible device recognised)
– If only LED X1 flashes red: error in the bus node
– If X1 and X2 flash red simultaneously: no device
connected to the bus node (at least one device is
required)
LED is off:
– No device is connected to the bus node
1)
Separate accessory with two interfaces for connection of an
additional device required
2)
Display depends on whether the connected device monitors the
load voltage and reports to the bus node
MNS – Module status/network status
(combined module/network status)
LED
Status and significance
display
LED illuminated green:
– Normal operating status ("online")
– Communication with the fieldbus is OK
LED flashes green:
– Fieldbus communication available ("online"),
but not configured
LED illuminated red:
– No fieldbus communication
(not available, failed or invalid bus address)
– No power supply to bus
chap. 4
LED flashes red:
– Communications error (fieldbus communication
faulty, bus time-out or no power supply to bus
chap. 4)
LED is off:
– No network or fieldbus connection (not "online",
MAC-ID test "DUB_MAC_ID" did not run successfully
or no power supply to bus
chap. 4)
IO= I/O status, connection status
LED
Status and significance
display
LED illuminated green:
– Normal operating status, communication with the
controller (PLC) OK
– IOs are controlled through the fieldbus
LED flashes green:
– Operating status in preparation
– IOs are in the idle status
LED illuminated red:
– Inputs/outputs are in the fail-state mode; cause is an
unrecoverable fault (e.g. no bus voltage)
LED flashes red:
– Failure or stop of PLC, fieldbus interruption or
telegram failure
– IOs are in the fail-state status
– Incorrect station number in the PLC or bus node
(incorrect DIL-switch position)
LED is off:
– Commissioning of the bus node not complete or not
successful
– Fieldbus not connected
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 Technical data
General properties
Note
Protection class through housing
(as per EN 60529)
Protection against electric shock
(protection against direct and
indirect contact acc. to
www.festo.com
EN 60204-1)
Galvanic isolation
Vibration and shock resistance
3)
(as per EN 60068)
– Vibration (part 2 – 6)
– Shock (part 2 – 27)
– Continuous shock
(part 2 – 29)
Temperature range
1)
– Storage/transport
– Environment/operation
Materials
1)
– Housing
– Fibre-optic cable, DIL switch
cover
– Threaded sleeve M12
– Threaded bush M3
– Seals
– Screws
1)
Requirement: bus node mounted completely, plug connector
plugged in or provided with protective cap
2)
Observe that connected equipment (devices) may fulfil a lower
protection class or lower temperature range
3)
Explanation of the severity level
on vibration and shock – severity level"
Power supply
Power supply to bus node/equipment
– Operating voltage (nominal
value/tolerance range, polarity-safe)
– Load voltage (maximum value/typical
tolerance range, device-dependent)
Bus power supply
(fieldbus interface)
– Tolerance range, polarity-safe
– Current consumption, interface
electronics
Intrinsic current consumption of bus node
at 24 V
– Bus node electronics
– Bus node on device (e.g. valve terminal)
– Bus node on electrical connection box,
type CAPC-... (X
and X
)
1
2
Load capacity of the operating and load
1) 3)
voltage supply
– Bus node on device (e.g. valve terminal)
– Bus node on electrical connection box,
type CAPC-... (X
and X
)
1
2
Mains buffering time
1)
Separate, external fuses are required for operating and load
voltage supply
2)
Dependent on the connected equipment/devices
(e.g. valve terminal)
3)
Load capacity with regard to the connected equipment, e.g. the
valve terminal, including the bus node
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical data of the connected equipment can be
found in the respective program documentation.
Explanation on vibration and shock – severity level
Severity level 1
Vibration;
(SL1, as per EN 60068,
0.15 mm path at 10 ... 58 Hz;
2 g acceleration at 58 ... 150 Hz
part 2 – 29)
Shock:
± 15 g with 11 ms duration;
5 shocks per direction
Continuous shock:
± 15 g with 6 ms duration;
1000 shocks per direction
Severity level 2
Vibration;
(SL2, as per EN 60068,
0.35 mm path at 10 ... 60 Hz;
5 g acceleration at 60 ... 150 Hz
part 2 – 27)
Shock:
± 30 g with 11 ms duration;
5 shocks per direction
Continuous shock:
n. a.
en
1) 2)
IP65/67
Through the use of PELV circuits
All bus signals, including
V – ("CAN_GND") and
V + ("CAN_V+"), are galvanically
isolated
3)
Severity level (SL)
for wall or
H-rail mounting
– Wall: SL2; H-rail: SL1
– Wall: SL2; H-rail: SL1
– Wall and H-rail: SL1
- 20 ... + 70 °C
- 5 ... + 50 °C
RoHS-compliant
PA, reinforced
PC
Brass, galvanically nickel-plated
Brass
NBR
Steel, galvanized
following table "Explanation
1)
24 V DC ± 25%
(18 ... 30 V DC)
Max. 30 V DC
2)
2)
(18 ... 30 V DC)
11 ... 30 V DC
Max. 50 mA
Max. 65 mA
Max. 120 mA
Max. 175 mA
Max.
4 A
Max.
2 A
10 ms
Note

Publicidad

Tabla de contenido
loading

Tabla de contenido