ABB Busch-Universal 6593U-500 Manual De Instrucciones página 73

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 202
Functions
1.1.1.44
Loads
-
Incandescent lamps
-
230 V halogen lamps
-
LV halogen lamps via Busch electronic transformers
-
LV halogen lamps via conventional transformers
CAUTION
Conventional transformers and Busch electronic
transformers must not be dimmed together.
All other load combinations are permissible.
Calculation of the Rated Power Output
Use the following formula to calculate the rated power
output:
Rated power output = Transformer losses* + luminaire
wattage
* with electronic transformers, 5% of the rated power
ofthe transformer
* with conventional transformers, 20% of the rated
power of the transformer

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Busch-universal 6594u-500

Tabla de contenido