Terminal board connection
Programmer power supply 230 Vac
1-2
3-4
Transformer power output 230 Vac
5
Programmer power supply earth wire
6
Motor earth wire
7
TB (NC contact) stop button input (The opening of this contact
interrupts the cycle until a new movement command is given).
CMN common for all inputs and outputs.
8
FTCS (NC contact) safety and control devices in input (stop photo-
9
electric cells). The opening of this contact will block all movement,
until the obstruction has been removed, due to the safety device
cutting in, the gate will then continue moving until it reaches a travel
limit (only in the automatic mode).
FTCI (NC contact) safety and control devices in input (photocells
10
invert the travel direction when an obstruction is detected). Opening
this contact will provoke a travel direction inversion during closure
due to the cutting in of the safety device.
CMN common for all inputs and outputs.
11
CSP safety buffer input NC/8.2 kΩ. Opening this contact will pro-
12
voke a travel direction inversion of 5 cm, a pause of 3 minutes,
after which the motor will continue moving in the original direction
after a 10 second preflashing period has elapsed.
13
LP 24 Vdc output for warning lights. 25 W intermittent activation
(50%), 12,5 W continuous activation.
CMN common for all inputs and outputs.
14
24 Vdc output, powering controlled external loads
15
All rights reserved. Unauthorised copying or use of the information contained in this document is punishable by law
CMN common for all inputs and outputs.
16
24 Vdc output, powering permanent external loads
17
CMN common for all inputs and outputs.
18
TA (NO contact) opening button input.
19
TAL (NO contact) limited opening button input.
20
TC (NO contact) closing button input.
21
22
TD (NO contact) dynamic button input.
23
CMN Common for all inputs and outputs.
24
LS 24 Vdc, 3W indicator light output.
25
EMRG 1 (NO contact) emergency manoeuvring button input 1
26
EMRG 2 (NO contact) emergency manoeuvring button input 2
L
230Vac
10
N
TRF 230Vac
7
8
9
10
11
12
13
19
20
21
22
23
24
B1
via radio
BC
Battery charger connector
CN1
Motor Faston connection
D1
Six-segment LED display
S1
Selection dip-switch
E1
Encoder connection
F1
3.1 A rapid fuse (24V battery powered operation protection)
F2
10 A rapid fuse (battery powered operation motor protection)
F3
10 A rapid fuse (motor power protection from transformer)
F4
3.1 A rapid fuse (24V transformer power protection )
(1)
.
.
(1)
L1
BC
CTRL
OUT
OUT
24Vdc
24Vdc
14
15
16
17
18
J4
27
Common for both emergency buttons.
28
Outer conductor for the radio receiver antenna
29
Inner conductor for the radio receiver antenna (if an external antenna is
fitted use a coaxial type cable RG58 with an impedance of 50Ω).
Note (
) The total of the 2 external device outputs must not exceed 10W.
1
ALL UNUSED NC CONTACTS MUST BE JUMPED and consequently the
security device test must also be deactivated (FTCI , FTCS - Dip 7 and Dip
OFF
and receiver parts of the security devices must be connected to the binding
CTRL 30 Vdc
delay between the command transmission and movement of the gate/s.
Switch on the power and make sure that the indicator LEDS are in the fol-
lowing condition (note: If the display is off you can press the PROG key to
show the status of the safety devices.
- L1 Power on
- L2 Transmitter code programming indicator
- L3
- L4
- L5
- L6
- L7
- L8
- L9
- L10
Note (
) The Leds are lit if the corresponding safety devices are not active.
2
Check that the activation of the safety devices switches the cor-
responding LEDS off.
If the green power on LED "L1" doesn't light up check the condition of
the fuses and the power cable connection at the transformer primary.
If one or more of the safety LEDS do not light up check the contacts
of the relative security devices and check that the unused safety device
contacts have been bridged.
Note: The safety inputs (TB, CSP, FTCI, FTCS) can either be set to work
as NC or 8.2 kΩ. Use parameter SC to set the required configura-
tion (see table on page 22).
R1
M1
J1
J2
Enable
CN1
J5
J1
Radio channel selection
J2
Enable transmitter memorisation via radio
J3
Emergency manouvring enable
M1
Transmitter code memory module
P1
Transmitter code memorization button (MEMO)
P2
Transmitter code cancellation button (DEL)
P3
Programming button (PROG)
R1
Radio frequency module, 433 MHz for S449 transmitters
J4
Battery connection
J5
Transformer secondary protection
17
FTCI, FTCS test both the transmission
TB
FTCI
FTCS
CSP
TA
TC
TAL
TD/CH1
L3
L6
L7
L9
B1
L4
L5
L8
L10
Disable
P1
J3
E1
25 26 27
M
ON
OFF
ON
(2)
ON
(2)
ON
(2)
ON
(2)
OFF
OFF
OFF
OFF
CS1318B
DC0434
D1
L2
P2
P3
S1