WIRING DIRECTIONS
Maximum CI-200s per power pack: B series = 5, BZ series = 7. When using more sensors than this, multiple power packs are required.
For all configurations—connect the low voltage:
• RED wire (+24VDC) from power pack to VIOLET wire on sensor.
• BLACK wire (Return) from power pack to GREEN wire on sensor.
Connections for the following configurations: (Refer to wiring diagram below)
Single lighting load controlled by occupancy only—connect:
• BLUE wire from power pack to yellow wire on sensor.
Single lighting load controlled by occupancy, dependent on light level (ambient light)—connect:
• BLUE wire from power pack to blue wire on sensor.
One lighting load for occupancy control, and a second load for occupancy and light level (ambient light) control—connect:
• BLUE wire from power pack to yellow wire on sensor.
• BLUE wire from slave pack to blue wire on sensor.
• BLACK wire from slave pack to gray wire on sensor.
Isolated Relay
(The Isolated Relay is rated for 1A @24VDC or 24VAC) Connect the wires necessary to the application that requires this output.
• RED (Common) (must be used for proper operation)
• BROWN (Normally Closed)—Open when occupancy is detected.
• ORANGE (Normally Open)—Closed when occupancy is detected.
White
POWER PACK
N
Hot
Black
SLAVE
PACK
Blue
Black
OFF switch
Light
Hot
Level
Lighting
Red (load)
Load
N
SENSOR ADJUSTMENT
The sensor comes factory preset and ready for operation. If testing of operation is desired:
• Remove the sensor's cover (twist).
• Refer to the DIP switch settings chart for switch configurations.
• Make sure that office furniture and fixtures are in place.
1. Restore power to the lighting circuits and turn the lights on.
• There is a one minute warm-up when power is initially restored to the sensor before the
sensor works properly.
2. For testing, set the Time Delay to minimum (15 secs.).
3. Set Sensitivity to maximum.
4. Turn Light Level Adjustment trimpot to maximum.
5. Replace the sensor's cover then move away from sensor and be still. The lights should go off
after 15 seconds. If lights remain on, see Unwanted Sensor Activations under Troubleshooting.
With movement in the area, the lights should turn back on.
6. If using the light level feature (otherwise skip to step 7), turn the adjustment trimpot to minimum,
and repeat step 5. Unless it is very dark, when the lights turn off, the lights controlled by light level
should not turn back on even with movement in the area. Until ready to make the final adjustment,
leave the setting at maximum. The controlled lights will then not be affected by ambient light levels.
To make the light level adjustment: (The final light level setting for normal operation should be
made at a time when, with the lights off, the ambient light level is at the point where it is desired
for the lights to turn on.)
White (Neutral)
Lighting
Red (Line)
Load
Switch
Red (Load)
Wires
Isolated Relay Outputs
Normally Closed Contact
1-BRN
Common
2-RED
Normally Open Contact
3-ORN
Control Output 24VDC
4-YEL
Control Return
5-GRN
Light Level Output 24VDC
6-BLU
+24VDC
7-VIO
Common
8-GRA
Visit our web site: www.wattstopper.com
CI-200
DIP Switch Control
for Time Delay and
Sensitivity
MAX
MIN
Light Level
Adjustment
LED
DIP Switch #
Time delay
15 seconds
2 minutes
4 minutes
6 minutes
8 minutes
10 minutes
12 minutes
14 minutes
16 minutes
18 minutes
20 minutes
22 minutes
24 minutes
26 minutes
28 minutes
30 minutes
Service
DIP Switch #
Sensitivity
Minimum
Medium Low
Medium High
Maximum
= ON
= OFF
= Factory Presets
1 2 3 4 5 6
7 8