Installation Instructions - Bradley On-Site S19-881 Instrucciones De Instalación

Lavador de ojos de alimentación por gravedad
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

®
On-Site
Gravity-Fed Eye Wash
S19-881

Installation Instructions

Step 1: Mount eye wash pedestal to wall (optional)
CAUTION: Eye wash station weighs 60 lbs when filled to capacity. Mounting bracket
screws and wall anchors must be strong enough to support the filled unit.
1. To mount the pedestal to the wall:
• Secure the mounting bracket to the wall with screws and wall anchors (provided by installer).
• Attach the pedestal to the mounting bracket at the handles on the back of the unit (see Figure 1).
Note: When mounting the eye wash unit to the mounting
bracket, make sure the unit is level and the sprayheads are
at a height of 33-45" from the floor and situated at least
6" from the wall or nearest obstruction (ANSI Z358.1-1998).
Step 2: Fill and mount tank
1. Pour clean, potable room temperature water into the
tank; continue pouring until the tank is 1/3 to 1/2 full.
2. Pour entire contents of the water preservative bottle
(supplied) into the eye wash tank.
3. Add clean, potable room temperature water
to the tank until the water level reaches the
top of the tank.
4. Insert one liner into the cap (with hole) and
attach the cap to the top of the tank (make
sure the cap is tightly closed) (Figure 2a).
5. OPTIONAL HEATER JACKET: Insert the
tube from the drain hole at the bottom of
the pedestal through the hole in the back of
the heater jacket. Drain hole location is
shown in Figure 2b on page 5.
NOTE: Make sure to insert the tube into the
pinch to prevent leaking when installing the tank.
OPTIONAL HEATER JACKET NOTE: Loosen the jacket around the pedestal to ease tank installation.
6. Invert the tank and place it on top of the pedestal as shown in Figure 2b found on page 5. The pierce
on the pedestal will puncture a hole in the tank cap liner and allow the solution to flow. Make sure
that the locking tabs are in front of the pedestal.
7. Secure the tank to the pedestal at the locking tabs with the two locking screws provided (see Figure
2a for locking tabs).
8. OPTIONAL HEATER JACKET: Insert the 5-pin connector into the mating socket on the junction
box and screw tight.
9. OPTIONAL HEATER JACKET: Slide the heater jacket up to cover the tank and secure the jacket
with the hook-and-loop fasteners.
10. OPTIONAL HEATER JACKET: Slide the arm into pocket of the jacket flap.
11. Raise the arm to snap fit in an upright position (this will automatically release the pinch).
NOTE: After the tank is mounted to the pedestal, minor spillage could occur. Allow the fluid to stabilize
completely before inspecting the unit for leaks.
4
9/11/03
Figure 2a
Bradley Corporation • 215-1271 Rev. H; EN 03-554
Installation Instructions
Figure 1
WALL
BRACKET
Turn cap to close
LOCKING
TAB