Soft Starter 3RW40 5, 3RW40 7
Read and understand these instructions before installing, operating, or maintaining the equipment.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device
before working on this device.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
The terminals of the motor control device must not be touched when it is connected to a voltage in order to prevent electrical shocks or
burning. The output terminals of the motor control device are connected to a voltage even when it is in the OFF state.
NOTICE
The 3RW40 soft starter was designed as device with radio suppression level Class A. The use of this product in inhabited areas may lead to radio
interference.
Stand-alone installation spacings (see soft starter manual for side-by-side installation)
≥ 100 mm
[≥ 4 in]
1
5
3
1
≥ 5 mm
≥ 5 mm
[≥ 0.2 in]
[≥ 0.2 in]
4
6
2
≥ 75 mm
[≥ 3 in]
Setpoint values for motor current
Permitted setpoint values for the motor current, dependent on the CLASS setting at 40 °C surrounding air temperature
I
[A]
e
3RW40 55-...
134
3RW40 56-...
162
3RW40 73-...
230
3RW40 74-...
280
3RW40 75-...
356
3RW40 76-...
432
Programming the ON/RUN output 13/14 (factory setting: ON) (Fig. 3 in graphics section)
1. Start programming mode: Press and hold the "RESET MODE" button (2) for longer than 2 seconds until the LED "DEVICE" (5) flickers green.
While pushing the "RESET MODE" button (2), press the "RESET/TEST" button (1) for longer than 1 second until the LED "DEVICE" (5) on the
device lights up red.
2. Display mode: LED "STATE/BYPASSED" (6) flashes green: ON mode. LED "STATE/BYPASSED" (6) flickers green: RUN mode.
3. Change mode: Press the "RESET MODE" (2) button.
4. Exit programming mode and save settings: Press and hold the "RESET/TEST" button (1) for longer than 1 second until the LED "DEVICE" (5)
lights up green.
6
CAUTION
Reliable functioning of the equipment is only ensured with certified
components.
NOTICE
Please adhere to the specified spacings when installing the device so that sufficient air can
circulate for ventilation. The unit is ventilated from bottom to top.
CAUTION
Risk of damage to property.
Ensure that no liquids, dust or conductive parts enter the soft starter.
NOTE
Surrounding air temperature - A rating assigned to open type equipment that refers to the
maximum ambient temperature of air immediately surrounding the equipment inside of the
ultimate enclosure.
I
[A]
I
[A] CLASS 10
min
max
59
134
87
162
80
230
130
280
131
356
207
432
I
[A] CLASS 15
I
[A] CLASS 20
max
max
134
124
152
142
210
200
250
230
341
311
402
372
English
3ZX1012-0RW40-1AA1

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Sirius 3rw40 5Sirius 3rw40 7

Tabla de contenido