OPERATING INSTALLATION MANUAL FOR AHU-KIT UNIT
(2) Put the thermistor cable in an individual protective tube.
(3) Apply stress release in the temperature sensor wire to prevent the temperature sensor
wire from getting loose due to stress. Stress or looseness of temperature sensor wire will
lead to poor contact and inaccuracy of temperature measuring.
Fixation of the thermistor
Notes:
① Put the thermistor wire slightly down to avoid water accumulation on top of the thermistor.
② Keep the thermistor and air handling unit in good contact. Put the top of the thermistor on
the air handling unit, because the top of thermistor is the most sensitive part. Please
fixing the thermistor on the horizontal plane of copper tube (within ±30°), and make them
close together.
(1) Fix the thermistor with insulating aluminum tape in order to ensure good heat
transference.
(2) Cover the thermistor with rubber belt to prevent looseness of temperature sensor.
(3) Use two wire ties to bind the thermistor securely.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Fig.4.5.1.2
Fig.4.5.1.3
Fig.4.5.1.4
'
Fig.4.5.1.5