Battery Location
Premium AA alkaline batteries
are required when C-wire is
not available. When C-wire is
available, the batteries provide
a back-up source of power (this
will maintain the clock in the
event of a power outage).
1.) Gas/Elec Switch
If the system is a heat pump or electric furnace, the GAS/ELEC Switch must be set to
Elec. If your system is a gas or oil furnace, the switch must be set to Gas.
2.) O/B Terminal Switch
The O/B switch on this thermostat is factory set to the O position. This will accommodate
the majority of heat pump applications, which require the changeover relay to be
energized in Cool. If the heat pump being installed requires a B terminal, to energize the
changeover relay in Heat, the O/B switch must be moved to the B position.
3.) RC/RH Jumper Wire
This thermostat electrically connects the RC and RH terminals so a jumper wire is not
required. If the application provides a separate wire for RC and RH, clip the RC/RH
jumper. This will isolate both terminals so they can be independently used.
INSTALLER MENU
To prevent changes that may affect system performance, this thermostat has an INSTALLER'S
MENU and an USER MENU. The INSTALLER'S MENU provides access to every option, while
the USER MENU provides access to items that will not affect system performance. To access
the INSTALLER'S MENU press the Menu button for 8 seconds. The display will show item 30 in
the table below. Use Next and Back to navigate through menu items. Press
a menu setting.
Installer's Menu #
Description
(Hold Menu 8 Seconds)
30
Heat Cycle Rate (how often
the heat will turn on)
35
Cool Cycle Rate (how often
the cooling will turn on)
Compressor Lockout
50
(protects the compressor
from short cycling)
65
Maximum Heat Limit
(maximum set point for heat mode)
66
Minimum Cool Limit (minimum
set point for cool mode)
74
Schedule Type (set as either 7-Day,
5-1-1 Day or Non-Programmable)
(Installer Menu continued on next page)
3
3
1
2
or
to change
Settings
Default Setting
(flashing icons)
(Press
or
)
SLO – slow
MEd
MEd – medium
FAS – fast
SLO – slow
MEd
MEd – medium
FAS – fast
On – 5 minute display
OFF
OFF – no delay
99
47 to 99
45
45 to 97
7 – 7 Day
5
5 – 5-1-1 Day
0 – Non Programmable
INSTALLER MENU (C0ntinued)
Installer's Menu #
Description
(Hold Menu 8 Seconds)
Early Start (starts heating or
cooling early so your programmed
76
temperature is reached by the
programmed time)
79
Fahrenheit or Celsius
Temperature Display
81
Adjustment (adjust the displayed
"Room Temperature")
Continuous Display Light (keep
83
the backlight always on – "C" wire
required)
86
Change Air Filter (set up a
monthly reminder)
Keypad Lock (prevent unwanted
99
changes to the thermostat)
TEST EQUIPMENT
Turn on power to the system.
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
1.) Move fan switch to On position. The blower should begin to operate.
2.) Move fan switch to Auto position. The blower should stop immediately.
Heating System
1.) Move System Switch to Heat position.
2.) Press
to adjust thermostat setting to 1° above room temperature. The system should
begin to operate and the thermostat will indicate Heat On.
3.) Press
to adjust thermostat setting 1° below room temperature. The heating system
should stop operating and the thermostat should indicate Heat.
Cooling System
1.) Move System Switch to Cool position.
2.) Press
to adjust thermostat setting 1° below room temperature. The blower should
come on immediately on high speed, followed by cold air circulation. The thermostat will
indicate Cool On. There can be up to a 5 minute delay. (see INSTALLER MENU, item 50)
3.) Press
to adjust thermostat setting to 1° above room temperature. The cooling system
should stop operating and the thermostat will indicate Cool.
Note: If Starting Soon is shown on the display, the compressor lockout feature is operating.
There will be up to a 5 minute delay before the compressor turns on.(see INSTALLER MENU,
item 50)
!
To prevent compressor and/or property damage, if the outdoor temperature is below 50°F,
DO NOT operate the cooling system.
Do not allow the compressor to run unless the compressor oil heaters have been operational
for 6 hours and the system has not been operational for at least 5 minutes.
Default Setting
Settings
(flashing icons)
On – start early
OFF
OFF – start at program
period time
°F – Fahrenheit
°F
°C – Celsius
0
-5 to +5
On – always on
OFF
OFF – momentarily
1 to 12 – reminder time
OFF
(months)
OFF – no filter reminder
On – disable buttons
OFF
OFF – all buttons are
active
CAUTION
4