18.
Adjust height of cover support collar flush to just below the finished floor. Cover support collar is adjustable for
finished floors of 0 inches to .25 inches [0.0 - 6.4 mm] thick. Tighten mounting screws [11] to 10 - 15 lbs-in torque
[1.1 - 1.7 N-m]. For thicker floor finishes use accessory collars (CFB8RCVRR series), sold separately.
19.
Seal the gap around the cover support collar [10] with a continuous bead of electrical grade type RTV silicone sealant
(SEE FIGURE E).
20.
Use the provided floor gasket or apply a 1/4 inch [6.3 mm] thick continuous bead of electrical type of RTV silicon
sealant compound fully around the perimeter on the underside of the flange [12].
21.
Attach flange [12] to the cover support collar [10] using #8-32 flat head screws [13] provided with the cover.
13
12
SEAL ALL AROUND
FIGURE
E
CFB10G55R/CFB10G55RCR 10 GANG RECESSED FLOOR BOX FOR
ROUND COVER Installation Instructions
CAUTION: RISK OF ELECTRICAL SHOCK. Disconnect power before installing or servicing.
NOTICE: For installation by a qualified electrician in accordance with all national and local electrical codes,
communications standards, the following instructions and any instructions included with individual devices.
NOTICE: Insure data/communications circuits are separated from lighting/power circuits in accordance with the NEC and
CE Code requirements.
Use with CFBS1R8CVRxx series round covers.
BEFORE CONCRETE POUR, SEE FIGURE A
1.
Remove four #8-32 pan head screws [1] from
top corners of floor box assembly and retain.
2.
Remove transition [2] and mounting plate [3]
assemblies from box and retain.
3.
Install leveling screws [4] as shown in FIGURE A.
4.
Make conduit connections in accordance with
application and applicable electric codes.
5.
For feed-thru wiring, remove non-metallic
dividers [5] as necessary.
6.
Reinstall transition [2] on top of the mounting
plate assembly [3]. Secure using #8-32 pan
head screws [1] in corners.
7.
Cover visible openings and screws that
penetrate the floor box with duct tape to
prevent concrete from entering the box.
8.
Position the floor box with the temporary cover
[6] even with slab level. Use leveling screws [4]
and wire to keep the floor box from moving
during concrete pour. Minimum depth of pour
is 6.50 inches [165.1 mm]
9.
Verify that flat head screws [7] holding the
temporary cover [6] are secure. After
tightening, cover screw heads with duct tape.
10.
Pour concrete flush to the top of the temporary
cover [6].
Wiring Device - Kellems
Hubbell Incorporated (Delaware)
40 Waterview Dr.
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com
PD2594
04/14
ENGLISH
7
6
1
2
3
5
4
FIGURE
A

Publicidad

loading

Resumen de contenidos para Hubbell CFBS1R8CVR Serie

  • Página 1 Pour concrete flush to the top of the temporary SEAL ALL AROUND cover [6]. FIGURE FIGURE Wiring Device - Kellems Hubbell Incorporated (Delaware) 40 Waterview Dr. Shelton, CT 06484 1-800-288-6000 www.hubbell-wiring.com PD2594 04/14...
  • Página 2 AFTER CONCRETE POUR, SEE FIGURES B, C, D, & E Orient cover support collar [10] as required by removing and reinstalling screws [11]. Lap joint in collar defines the hinge location of the cover (SEE FIGURES C & D). Locate floor box, remove three screws [7] and remove temporary concrete cover [6]. CAUTION: Temporary concrete Install finished flooring to within 1/8 inch [3.2 mm] of cover support collar [10].
  • Página 3 FIGURE Couler le b ton de niveau avec le couvercle temporaire [6]. FIGURE Wiring Device - Kellems Hubbell Incorporated (Delaware) 40 Waterview Dr. Shelton, CT 06484 1-800-288-6000 www.hubbell-wiring.com PD2594 04/14...
  • Página 4 Orienter le collier de soutien du couvercle [10] au besoin en retirant et en r installant les vis [11]. Le joint de APR S LA COUL E DU B TON, CONSULTER LES FIGURES B, C, D ET E recouvrement du collier repr sente la partie charni re du couvercle (consulter les FIGURES C et D). Localiser la bo te de plancher, retirer les trois vis [7] et le couvercle temporaire [6].
  • Página 5 FIGURA Wiring Device - Kellems HUBBELL DE M XICO garantiza este producto, de estar libre de defectos en materiales y mano de obra por un a o a partir de su compra. Hubbell reparar o reemplazar el Hubbell Incorporated (Delaware) art culo a su juicio en un plazo de 60 d as.
  • Página 6 Orientar el collar n de soporte de la tapa [10] seg n la necesidad retirando y reinstalado los tornillos [11]. La junta de DESPU S DEL COLADO DEL HORMIG N, VER FIGURAS B, C, D y E solape en el collar n define la ubicaci n de la bisagra de la tapa (VER FIGURAS C y D). Ubicar la caja para piso, retirar tres tornillos [7] y la tapa temporal para hormig n [6].

Este manual también es adecuado para:

Cfb10g55rCfb10g55rcr