2. DESCRIPTION
Fully configurable
Low battery voltage alarm trip and reset levels
Low battery voltage cut-off and restart levels, or Dynamic cut-off
Output voltage 210 - 245V
Frequency 50 Hz or 60 Hz
2.1 High efficiency
The overall maximum efficiency of the inverter RS is over 96%.
The inverter is short circuit proof and protected against overheating, whether due to overload or high ambient temperature.
2.2 High voltage MPPT solar controller
Two strings can be connected to the inputs. Both are wired parallel to one tracker, therefore the two strings must be equal in number of
solar panels and type. The total allowed input current is limited by the device to 18A.
! Do not connect PV with a potential current greater than 20A as this could damage the device.
When the MPPT switches to float stage it reduces the battery voltage by increasing PV voltage (reducing the total solar power output).
For this system to work, the maximum open circuit voltage of the PV array must not be higher than 8 times the minimum battery voltage
when at float, to an absolute maximum of 450V. Exceeding these open circuit PV voltage limits is forbidden and will lead to system
shutdowns and damage to the device.
Example PV Configurations
Panel type
Voc
Ja solar 300W
39.85V
(60Cells)
Panasonic HIT
70.9V
N325K (96Cells)
SunPower X22
69.5V
360W (96Cells)
Victron 330W
44.72V
(70cells)
2.3 Frequency shift function
When external PV inverters are connected to the output of the inverter, excess solar energy is used to recharge the batteries, just as
with the internal MPPT solar controller. Once the battery absorption voltage is reached, charge current will reduce by shifting the output
frequency higher. This feature is used for battery over charge protection and solar assist. It does not allow charging the battery to fully
charge to 100% SoC for safety reasons.
2.4 High peak power
The inverter is capable of providing 50Amp AC or 9000W for a short time.
2.5 Interfacing
Bluetooth
VE.Direct
VE.Can
User I/O connector:
Aux 1, 2 input
Programmable relay
Battery Vsense
Battery Tsense
Remote H/L on off *
* Remote L functions as 'allow to charge' in case lithium battery is selected and remote H functions as 'allow to discharge'. Use
miniBMS for the inverter RS with Victron lithium batteries.

2.6 Battery charger

The batteries are charged by solar energy using the built-in MPPT solar controller. It can also be charged by a PV grid inverter
connected to the AC out. In this case the battery will be charged to ~98%. The built-in MPPT has a power limit of 4000W. So the
maximum charging current for a 50V battery will be 80A. If an additional PV grid inverter is connected (max 5000W) the maximum total
charging current is limited to 100A. The maximum charging current of 100A is reduced if battery voltage goes above 60V. A custom
maximum charge current value can also be defined by the installer in VictronConnect.
The charger algorithm is the same as for the BlueSolar MPPT solar controllers. This provides built-in battery preset parameters, and
allows for expert mode to define additional charging parameters. Please see the MPPT section of the VictronConnect manual for
additional explanation of these charging features.
2
Vmpp
Isc
Impp
32.26V
9.75A
9.3A
59.2V
5.94A
5.5A
59.1V
6.48A
6.09A
37.3V
9.57A
8.86A
Nr of
Max
Ptot
pannels
String
voltage
2x7
279V
4200W
2x6
425V
3900W
2x6
417V
4320W
2x6
268V
3960W