DAB MCE-22/C Instrucciones De Instalación Y Mantenimiento página 51

Ocultar thumbs Ver también para MCE-22/C:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 97
See Figure 5 for an example of connection.
5.5.3
Outputs
The connections of the outputs listed below refer to the two 3-pole terminal boards J3 and J4 indicated with
the screen-printing OUT1 and OUT2 below which is also indicated the type of contact for the terminal
(NC = Normally Closed, C = Common, NO = Normally Open).
Characteristics of the output contacts
Type of contact
Max. bearable voltage [V]
Max. bearable current [A]
Max. accepted cable section [mm²]
Table 5: Characteristics of the output contacts
Functions associated with the outputs
OUT1
Presence/Absence of alarms in the system
OUT2
Pump running/Pump stopped
In the example shown in Figure 6 the light L1 is lit when there is an alarm in the system and it goes off when
no kind of malfunction is found, whereas the light L2 is lit when the pump is running and goes off when the
pump is stopped.
ENGLISH
Figure 5: Example of Connection of Analogue Input
NO, NC, COM
250
5
If resistive load
2.5
If inductive load
3.80
50

Publicidad

Tabla de contenido
loading