Connecting Dc Power - Rockwell Automation Allen-Bradley PanelView 550 Instrucciones De Instalación

Terminales de pantalla táctil
Ocultar thumbs Ver también para Allen-Bradley PanelView 550:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

10
PanelView 550/600 Touch Screen Terminals

Connecting DC Power

All of the PV550/600 touch screen terminals (e.g., Catalog No. 2711-T5A1L1 or
2711-T6C8L1) connect to a 24V dc power source.
The table below shows the electrical ratings for the DC versions of the terminals.
Electronic circuitry and an internal fuse protect the terminals from reverse
polarity and over-voltage conditions.
Terminal Type
PV550 Touch
PV600 Touch
ATTENTION: Do not connect the PanelView terminal to an AC power
!
source. Connecting to an AC power source may damage the terminal.
ATTENTION: The PanelView 550/600 terminal is designed for safe use
!
when installed in a suitably rated NEMA Type 12, 13, 4X (indoor use
only), IP54 or IP65 enclosure.
ATTENTION: Use only a Safety Extra Low-Voltage (SELV) power
!
supply as a source for the PanelView 550/600 terminal. A SELV power
supply does not exceed 42.4V dc.
41061-109-01(B)
Supply Voltage
18 to 32V dc,
(24V dc nominal)
18 to 32V dc,
(24V dc nominal)
Power Consumption
18 Watts max. (0.75 Amps @ 24V dc)
17 Watts max. (0.71 Amps @ 24V dc)

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Allen-bradley panelview 600

Tabla de contenido