Installation

Installation

Supplies Required:

• (3) 3/8" floor anchors and bolts
• Teflon tape and pipe sealant
• Piping to 1-1/4" NPT water supply inlet on unit
with adequate supply pipe supports
• Minimum 4" drain to accommodate 30 gallons per
minute discharge for drench shower waste
• Electrical supplies to connect to unit junction box
IMPORTANT: Bottom supply units have
provisions for supporting the top of the unit.
The 1-1/4" NPT solid pipe protruding from
the shell must be used to support the unit.
Step 1: Secure unit to floor
1. Install three suitable anchors (supplied by
installer) for 3/8" bolts in the floor.
2. Bolt the base to the floor anchors using 3/8"
bolts (supplied by installer).
3. Install the pull rod to the unit as shown.
IMPORTANT: Do not rely on unit to support
supply piping.
IMPORTANT: Unit requires a minimum 30
GPM to operate and a minimum 30 PSI of
flowing water pressure. Preferred flowing
water pressure is 40-60 PSI. Water supply
to the unit must be freeze-protected (by
others).
IMPORTANT: Pipe size should be no smaller
than 1-1/4" (supplied by installer).
Step 2: Connect water supply
1. Connect the water supply piping to the 1-1/4"
NPT inlet on the unit (piping by installer).
Use pipe hangers or other means to provide
adequate supports for the supply pipe (supports
by installer).
2 Open water supply lines and test for leaks and
adequate water flow.
Step 3: Assemble components
1. Install the showerhead to the unit as shown. The bottom
edge of the showerhead should be 85-1/4" (2165mm)
from the floor.
2. Mount the safety signs to the wall or to the unit if
desired. Use the screws, nuts and hooks provided to
hang the signs back-to-back on the unit.
Step 4: Connect electrical supply
1. Connect the power to the junction box on the unit as
shown in the schematic on page 4 (junction box accepts
3/4" NPT conduit fittings).
2. Connect the optional alarm system and indicator light as
shown.
NOTE: Average power consumption of the unit is .7 amp/80
watts at 120VAC (.35 amp/80 watts at 220/240 vac) at 50°F
(10°C) internal unit temperature. Refer to the installation
instructions provided with the alarm system for more
information.
Bradley Corporation • 215-1082 Rev. F; ECN 08-521
Junction Box 3/4"
NPT Hub
19-1/4"
(489mm)
94-5/8"
(2405mm)
60-3/4"
(1543mm)
39-1/2"
(1004mm)
43"
(1089mm)
Ø 9" (229mm) Flange with
(3) Ø 3/8" (10mm) Holes on
a Ø 8" (203mm) Bolt Circle
Use tefl on tape
only with plastic
showerheads.
Safety signs
shown mounted
back-to-back.
9/26/08
S19-300T, S19-300B
Top Supply
1-1/4" NPT
37-3/4"
(959mm)
25-3/4"
(654mm)
85-1/4"
(2165mm)
9-3/4"
(245mm)
68"
(1724mm)
35-1/2"
(900mm)
Bottom Supply
1-1/4" NPT
Bottom supply units
must use this pipe for
supporting unit.
3/4" NPT
Junction Box
opening
92"
(2337mm)
6"
(152mm)
3