Receiving Inspection
Upon receiving the pump, it should be inspected for
damage or shortages. If damage has occurred, file a claim
immediately with the company that delivered the pump.
If the manual is removed from the packaging, do not lose
or misplace.
Storage
Any product that is stored for a period longer than six (6)
months from the date of purchase should be bench
tested prior to installation. A bench test consists of,
checking the impeller to assure it is free turning and a run
test to assure the motor (and switch if provided) operate
properly. Do not pump out of liquid.
IMPORTANT! A clearance under the
WARNING
pump for entrance of sewage solids
must be a minimum of 3 inches to a maximum of 4.5
inches.
Submergence
The pump should always be operated in the submerged
condition. The minimum sump liquid level should never
be less than above the pump's volute (see figure 3)
Installation
The sump or basin shall be sealed and vented in accor-
dance with local plumbing codes. This pump is designed
to pump domestic wastewater, nonexplosive and non-
corrosive liquids and shall NOT be installed in locations
classified as hazardous in accordance with the
National Electrical Code
(NEC) ANSI/ NFPA 70
or Canadian Electric
Code (CEC). The pump
should never be
installed in a
trench, ditch,
or hole with
a dirt bottom.
The legs will
sink into the
dirt and the
suction will
become
plugged.
FIGURE 3
Grinder Pumps
Models: AGP300, AGP500 & AGP750
Receiving and Installation
Discharge Piping
Install discharge piping or hose assembly to the pump.
Discharge piping should be as short as possible and sized
no smaller than the pump discharge. Do not reduce the dis-
charge pipe size below that which is provided on the pump.
Both a check valve and a shut-off valve are recommended
for each pump. The check valve is used to prevent backflow
into the sump. The shut-off valve is used to manually stop
system flow during pump servicing. Be sure the discharge
pipe has a 1/8" diameter hole approx. 5" from end nearest
volute and oriented towards the pump body.
Control Panel
All pumps require a control panel. Single phase models
require start components in panel.
Motor
Each motor is provided with heat sensor thermostats
attached directly to the motor windings. The
thermostats open if the motor windings see excessive heat
and, in turn, open the motor contactor in the control panel
when used, breaking the power to the pump. When the
motor is stopped due to an overheated condition, it will
not start until the motor has cooled.
Motor Seal Failure Warning
On three phase models,the seal chamber is oil filled and
provided with moisture sensing probes to detect water
leakage through the lower shaft seal. The probes can also
detect moisture present in the upper motor housing.
The presence of water energizes a red seal leak warning
light at the control panel. This is a warning light only, and
does not stop the motor. It indicates a leak has occurred
and the pump must be repaired. Normally, this indicates
the outboard seal has leaked. Allowing the unit to operate
too long after the warning could cause upper seal
leakage along with motor failure.
The resistance across the moisture sensing (seal failure)
probes should be checked after a seal leak warning light
has lit. This can be done by disconnecting the red and or-
ange control wires from the control panel, and measuring
the resistance with an ohmmeter between the wires.
The reading should be 100,000 ohms or greater. If the
measured values are below those indicated above, then
the pump may have a lower seal failure and require service.
Note: Failure to use proper circuitry and to connect the
motor overheat protection in the control panel would ne-
gate all warranties.
Motor Power Cord, Control Cord And Cord Cap
Assembly
Each motor power cord has 4 conductors: white, black, red
and green.
For three phase motors the red, black and white conduc-
tors connect to the three line leads, and the green is con-
nected to a good ground. Interchanging any two line leads
will reverse the rotation of the motor
(see figure 4, page 6 )
5