ISU # Description
8140
Humidification
control
9100
Dehumidification
equipment
9140
Dehumidification
equipment setup
9160
Dehumidification -
overcooling limit
9180
Dehumidifier fan
control
10100
Ventilation type
10160
Ventilation fan
control
10240
Ventilation percent
on time
10280
Ventilation low
temperature lockout
Setting
0 = Humidify only when heat is On
1 = Humidify only when fan is On
2 = Humidify on demand: Thermostat controls fan
3 = Humidify on demand: Humidifier controls fan
0 = None
1 = A/C with low speed fan
2 = A/C with high speed fan
4 = Whole house dehumidifier
0 = Normally open
1 = Normally closed
0, 1, 2, 3°F
0.0, 0.5, 1.0, 1.5°C
0 = Thermostat controls fan
1 = Equipment controls fan
0 = None
1 = ERV / HRV
2 = Passive (fan only)
3 = Fresh air damper
0 = Thermostat controls fan
1 = Equipment controls fan
10% to 100% (in 10% increments)
Off
-20°F to 40°F (in 5°F increments)
-29.0°C to 4.5°C (in 2.5°C or 3.0°C increments)