Remove the 1-2 contact bridge
1
2
Magnetic contact for
left fixed door
CONNECTION SEQUENCE
The connection sequence creates a series of closed contacts with the doors in normal sliding
operating position. Breaking through either door will cause the opening of the series, immediately
arresting the sliding movement.
1 - remove the "total stop" bridge from terminals 1-2
2 - insert a left magnetic contact terminal and one right magnetic contact terminal
3 - insert remaining left and right magnetic contact terminals in the connection terminal board to the
spiral cables
4 - connect the spiral cables from the terminal board to the carriage terminals and from these to the
upper contact cap
5 - connect the contacts of the lower contact cap.
Checks
- Check that the caps' contacts are aligned in the reinforced door position.
- Align the magnetic contacts in closed fixed door position.
- Check the conduction of the connection heads to terminals 1-2 with an ohm tester.
Note: If the antipanic system and an automatic (CORSA or RODEO) door are ordered together,
part of the connections described and the application of the spiral cables will have already been
done.The installer will only need to connect the magnetic contacts and the mobile doors.
Power connections
Power connections
Power connections
Power connections
Power connections
Spiral cables
4
Contact caps
5
Contact bridge
CONTROL BOARD
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
10
1
2
3
4
3
4
Magnetic contact for
Contact bridge
2
right fixed door
- pg. 27 -