Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: NWTL-111-1P-V2/NWTL-111-2P-V2
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
The NWTL-111-1P-V2 and NWTL-111-2P-V2 are user-configurable wireless lighting control nodes operating on IEEE 802.15.4, 2.4GHz wireless
self-healing technology. Each node provides On/Off and 0-10V Dimming control and power monitoring, and is compatible with the ANSI 136.41
NEMA receptacle. The NWTL-111-xP is an intelligent lighting controller capable of stand-alone or network operation. It uses zero crossing
circuitry for reliability and increased product life. NWTL-111 version 2 nodes provide support for Wattstopper 24VDC occupancy sensors.
The NWTL-111-1P-V2 operates at 120/277/347 Volts. The NWTL-111-2P-V2 operates at 208/240/480 Volts. Both are designed for
outdoor or indoor applications.
• Unpack the NWTL-111.
• Inspect the device for missing or broken pieces/components.
• Read all included instructions prior to use.
The NWTL-111 should be mounted in a vertical orientation; ensuring
vertical polarity is maintained with the antenna. Fixed antenna devices
must be mounted with antenna positioned vertically.
The NWTL-111 is designed to be plugged into the ANSI 136.41 twist-lock
receptacle. Proper alignment should be verified by ensuring the high voltage
prongs are installed in the appropriate (size-specific) slots on the receptacle.
Following installation of the NWTL-111, the light will turn on by default
until commanded by the network, unless an internal schedule is present
commanding the light off.
1. Turn off all power at fuse or breaker box.
2. Ensure that the supply voltage matches the lighting voltage ratings.
3. Wire socket as indicated in wiring diagram.
4. Installation must be in compliance with NFPA National Electrical
Code which requires both sides of an ungrounded single phase or
multi-phase line be broken (article 410-48) for lighting loads.
5. To install the control, firmly place it into the socket and twist it
clockwise until it locks into place.
NOTE: If the dimming function is not working, it is likely that a
proper connection is not being made with the terminals on
the NWTL-111. Confirm that the unit is locked into place.
NOTE: The NWTL-111 socket must be mounted using a weatherproof
washer.
DESCRIPTION AND OPERATION
BEFORE INSTALLATION
MOUNTING
INSTALLATION
Wattstopper
BULIT
Wireless Control Node version 2
®
BULIT Tête de Contrôle Sans Fil version 2
BULIT Nodo de Control Inalambrico version 2
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
SPECIFICATIONS
Power
NWTL-111-1P-V2 (1 Phase) ............................. 120/277/347V
NWTL-111-2P-V2 (2 Phase) ............................. 208/240/480V
Active Power ........................................................................ 1000W
Radio ......................................................... 2.4GHz, , IEEE802.15.4
Range:. ................................................................ Up to 1000' range
Antenna: .........................................IPEX Connector, 2.4 GHz gain
Security .......................................................128-bit AES Encryption
Sensor Output .............................................. up to 15mA @ 24VDC
0-10V Dimming, via ANSI 136.41 receptacle
Compliant with FCC part 15
Occupancy
Sensor Input
(Orange Wire)
Load
(Switched L1)
(Red Wire)
Occupancy
Sensor Ouput
(Brown Wire)
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
®
WIRING
L2 (Line)
(Black Wire)
0-10 V Sinking Control
(10V supplied by driver)
Dimming –
(Violet Wire)
Occupancy Sensor
Common
0-10 V Sinking Control
(10V supplied by driver)
Dimming +
(Grey Wire)
For Single Phase –
Neutral
For Dual Phase –
L1 (Line)
(White Wire)

Publicidad

Tabla de contenido
loading

Resumen de contenidos para LEGRAND NWTL-111-1P-V2

  • Página 1 Compliant with FCC part 15 DESCRIPTION AND OPERATION The NWTL-111-1P-V2 and NWTL-111-2P-V2 are user-configurable wireless lighting control nodes operating on IEEE 802.15.4, 2.4GHz wireless self-healing technology. Each node provides On/Off and 0-10V Dimming control and power monitoring, and is compatible with the ANSI 136.41 NEMA receptacle.
  • Página 2: Wireless Connection

    WIRELESS CONNECTION When connected with the 225CWS Wireless Network Manager and other Wattstopper wireless devices, one or more NWTL-111s automatically creates a self-healing tree network. When powered up, the NWTL-111 first seeks the 225CWS (the host). If it finds a 225CWS with a signal strength of at least 70 on the Link Quality Indicator (LQI), it connects with that device.
  • Página 3 INSTRUCTIONS EN FRANÇAIS DESCRIPTION DE L’APPAREIL SPÉCIFICATIONS Alimentation ................... Les NWTL-111-1P-V2 et NWTL-111-2P-V2 sont des modules NWTL-111-1P-V2 (Monophasé) ......120/277/347 V de contrôle d’éclairage sans fil configurables par l’utilisateur NWTL-111-2P-V2 (2 pôles) ........208/240/480V et fonctionnant sous protocole IEEE 802.15.4, 2,4 GHz de technologie auto-adaptation sans fil.
  • Página 4: Connexion Sans Fil

    CONNEXION SANS FIL En cas de raccordement avec le 225CWS Gestionnaire de Réseau Sans Fil et d’autres appareils Wattstopper sans fil, un ou plusieurs NWTL-111 crée(nt) automatiquement une architecture de réseau d’auto-adaptation. Lorsqu’il est mis en marche, le NWTL-111 recherche d’abord le 225CWS (hôte). S’il détecte un 225CWS avec un signal d’au moins 90 selon l’indicateur de qualité de liaison (LQI), il se connecte à...
  • Página 5: Especificaciones

    INSTRUCCIONES EN ESPAÑOL DESCRIPCIÓN DE LA UNIDAD ESPECIFICACIONES Los NWTL-111-1P-V2 y NWTL-111-2P-V2 son nodos de control Alimentación inalámbricos configurables por el usuario que operan con NWTL-111-1P-V2 (Monofásico) .......120/277/347 V tecnología inalámbrica autorregenerable IEEE 802.15.4, 2.4GHz. NWTL-111-2P-V2 (2 fases) ........208/240/480 V Cada nodo proporciona control de intensidad de iluminación de...