The +19 [Vdc] power supplies to pins 11 and 18 and J5 (18-pole terminal board) can deliver a maximum of 50
[mA].
2.2.4.1
OUT 1 and OUT 2 output contacts:
The connections of the outputs listed below refer to the two 3-pole terminal boards J3 and J4 marked OUT1 and OUT 2, with a text
below indicating the type of terminal contact.
Type of contact
Max. admissible voltage [V]
Max. admissible current [A]
Max. admissible cable section [mm²]
Figure 10: Example of output connections
2.2.4.2
Input contacts (photocoupled)
The connections of the inputs listed below refer to the 18-pole terminal board J5, with numbering starting from pin 1 from the left. The
base of the terminal board also bears the text of the corresponding inputs.
-
I 1: Pins 16 and 17
-
I 2: Pins 15 and 16
-
I 3: Pins 13 and 14
-
I 4: Pins 12 and 13
The inputs can be activated in DC or AC (50-60 Hz). The following table shows the electrical specifications of the inputs: Table 7.
Minimum activation voltage [V]
Maximum deactivation voltage [V]
Maximum admissible voltage [V]
Current absorption at 12V [mA]
Max. admissible cable section [mm²]
N.B. Inputs can be controlled with both polarities (positive or negative with respective return to earth)
ENGLISH
Output contact specifications
NO, NC, COM
250
5
-> resistive load
2,5 -> inductive load
3,80
Table 6: Output contact specifications
Input specifications
DC inputs [V]
Table 7: Input specifications
80
With reference to the example in Figure 10 and using the
default settings (O1 = 2: contact NO; O2 = 2; contact NO)
the following is obtained:
L1 lights up when the pump is blocked (e.g.
•
"BL": water failure block).
L2 lights up when the pump is running ("GO").
•
AC inputs 50-60 Hz [Vrms]
8
2
36
3,3
2,13
6
1,5
36
3,3