14
MicroLogix™ 1200 Programmable Controllers

Wire Requirements

Wire Type
Solid
Cu-90°C (194°F)
Stranded
Cu-90°C (194°F)
Wiring torque = 0.791 Nm (7 in-lb) rated
ATTENTION: Be careful when stripping wires. Wire fragments
that fall into the controller could cause damage. Once wiring is
!
complete, be sure the controller is free of all metal fragments before
removing the protective debris strip. Failure to remove the strip
before operating can cause overheating.

Wiring Recommendation

When wiring without spade lugs, keep the finger-safe covers in place. Loosen the
terminal screw and route the wires through the opening in the finger-safe cover.
Tighten the terminal screw, making sure the pressure plate secures the wire.
1762-IN006A-ML-P
Wire Size (2 wire maximum per terminal screw)
#14 to #22 AWG
#16 to #22 AWG
Finger-safe cover