Charging

n If installed total piping length is more than standard total length, additional refrigerant charging is
necessary.
Below standard total piping length, additional refrigerant charging is not required.
Multiple Piping Models
Max total length of all
Outdoor Unit Ca-
pipes (A+B)/(A+B+C)/
pacity (Btu/h class)
(A+B+C+D)
24k
246(75)
36k
246(75)
Distributor Type Model
Outdoor Unit
Capacity
(Btu/h class)
48k
Important:
If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using
the charge amount specified on the Unit`s specification label.
Multiple Piping Models
Additional charge(oz ) = (Total Installation Piping Length-Standard Total Piping Length) x 0.22
EX) MR24DY3JMA
Max length of each
pipe (A/B/C/D)
82(25)
82(25)
Main Piping Length
Standard Length
Unit : g/m (oz/ft)
16.4(5)
a
b
c
Min length of each
pipe (A/B/C/D)
9.8(3)
9.8(3)
Additional
Standard
Refrigerant
0.55(50)
16.4(5)
Each branch pipe
9k
a=82ft
b=16ft
c=49ft
9k
❈ Additional Charge
= {(82+16+49)-74} x 0.22 = 16.06 oz
9k
Standard Total Piping
Additional Refrigerant
Length (No Add`l re-
Unit : g/m (oz/ft)
0.22(20)
74(22.5)
0.22(20)
98.4(30)
Branch Piping Length
Additional
Refrigerant
Length
Unit : g/m (oz/ft)
0.22(20)
Installation Manual 35
Charging
Unit: ft(m)
frigerant)
Unit: ft(m)