Re g i ste r d es c ript io n
INSTRUMENT GENERAL SETUP
MODBUS address
Communication speed
MODBUS mode
Phase 1 current full scale, according to the instrument:
• For 1/5A CT: CT primary (CT1
• For 80A: Reserved
• For Rogowski: Full scale (FSA1)
Phase 1 CT secondary (only for 1/5 CT instrument)
Phase 2 current full scale, according to the instrument:
• For 1/5A CT: CT primary (CT2
• For 80A: Reserved
• For Rogowski: Full scale (FSA2)
Phase 2 CT secondary (only for 1/5 CT instrument)
Phase 3 current full scale, according to the instrument:
• For 1/5A CT: CT primary (CT3
• For 80A: Reserved
• For Rogowski: Full scale (FSA3)
Phase 3 CT secondary (only for 1/5 CT instrument)
PT primary (only for 1/5 CT or Rogowski instrument)
PT secondary (only for 1/5 CT or Rogowski instrument)
Wiring mode
Mode for DMD value calculation
Integration time for DMD value calculation
INSTRUMENT GENERAL SETUP
Available only for instrument with RS485 port.
Available only for ENH instrument version.
70
)
pri
)
pri
)
pri
INTE G E R
F. code
Register
(Hex)
Words
(Hex)
03 / 04 / 10
2026
2
03 / 04 / 10
2028
2
03 / 04 / 10
202A
2
03 / 04 / 10
202C
2
03 / 04 / 10
202E
2
03 / 04 / 10
2030
2
03 / 04 / 10
2032
2
03 / 04 / 10
2034
2
03 / 04 / 10
2036
2
03 / 04 / 10
2038
2
03 / 04 / 10
203A
2
03 / 04 / 10
203C
2
03 / 04 / 10
203E
2
03 / 04 / 10
2040
2
P ro gr a mmabl e dat a
$01...$F7 (1...247)
$01=300 bps
$02=600 bps
$03=1200 bps
$04=2400 bps
$05=4800 bps
$06=9600 bps
$07=19200 bps
$08=38400 bps
$09=57600 bps
$00=7E2 (ASCII)
$01=8N1 (RTU)
Ph1 CT primary: $01...$C350 (1...50000)
FSA1: $01F4=500 A
$0FA0=4000 A
$4E20=20000 A
$01=1 A
$05=5 A
Ph2 CT primary: $01...$C350 (1...50000)
FSA2: $01F4=500 A
$0FA0=4000 A
$4E20=20000 A
$01=1 A
$05=5 A
Ph3 CT primary: $01...$C350 (1...50000)
FSA3: $01F4=500 A
$0FA0=4000 A
$4E20=20000 A
$01=1 A
$05=5 A
$00001...$F423F (1...999999V)
(for direct insertion, set PT
=1.
pri
PT
=1 will be set automatically)
sec
$50...$96 (80...150V)
(if PT
=1 > PT
=1 automatically preset,
pri
sec
not programmable)
$01=3 phases, 4 wires, 3 currents
$02=3 phases, 3 wires, 2 currents
$03=1 phase
$00=fixed window
$01=sliding window
$05=05 min
$0A=10 min
$0F=15 min
$1E=30 min
$2D=45 min
(not available with Sliding window mode)
$3C=60 min
(not available with Sliding window mode)
MODBUS RTU/ASCII, TCP