Algodue ELETTRONICA UPM209 Manual Del Usuario página 71

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Re g i ste r d es c ript io n
Maximum and DMD max value reset
Minimum value reset
DMD value reset
Energy counter reset
Real time clock
The writing command can be sent also in broadcast by
using $00 MODBUS address. For broadcast function, no
instrument response is sent.
Digital output mode
Digital output parameter
INSTRUMENT GENERAL SETUP
Available only for instrument with RS485 port.
MODBUS RTU/ASCII, TCP
INTE G E R
F. code
Register
(Hex)
Words
(Hex)
10
2042
2
10
2044
2
10
2046
2
10
2048
2
03 / 04 / 10
204A
2
03 / 04 / 10
204C
2
03 / 04 / 10
204E
2
P ro gr a mmabl e dat a
$01=V1, V2, V3, V12, V23, V31, V∑
$02=A1, A2, A3, AN, A∑
$03=+P1, +P2, +P3, +P∑
$04=-P1, -P2, -P3, -P∑
$05=+S1, +S2, +S3, +S∑
$06=-S1, -S2, -S3, -S∑
$07=+Q1, +Q2, +Q3, +Q∑
$08=-Q1, -Q2, -Q3, -Q∑
$09=+PF1, +PF2, +PF3, +PF∑
$0A=-PF1, -PF2, -PF3, -PF∑
$0B=+TAN1, +TAN2, +TAN3, +TAN∑
$0C=-TAN1, -TAN2, -TAN3, -TAN∑
$0D=THDV1, THDV2, THDV3, THDV12, THDV23, THDV31
$0E=THDA1, THDA2, THDA3, THDAN
$0F=A1
, A2
, A3
, A∑
DMD
DMD
DMD
DMD
$10=+P1
, +P2
, +P3
, +P∑
DMD
DMD
DMD
$11=-P1
, -P2
, -P3
, -P∑
DMD
DMD
DMD
$12=+S1
, +S2
, +S3
, +S∑
DMD
DMD
DMD
$13=-S1
, -S2
, -S3
, -S∑
DMD
DMD
DMD
$14=+Q1
, +Q2
, +Q3
, +Q∑
DMD
DMD
DMD
$15=-Q1
, -Q2
, -Q3
, -Q∑
DMD
DMD
DMD
$16=ALL
$01=P∑
$02=S∑
$03=Q∑
$04=ALL
$01=A1
, A2
, A3
, AN
DMD
DMD
DMD
DMD
$02=+P1
, +P2
, +P3
, +P∑
DMD
DMD
DMD
$03=-P1
, -P2
, -P3
, -P∑
DMD
DMD
DMD
$04=+S1
, +S2
, +S3
, +S∑
DMD
DMD
DMD
$05=-S1
, -S2
, -S3
, -S∑
DMD
DMD
DMD
$06=+Q1
, +Q2
, +Q3
, +Q∑
DMD
DMD
DMD
$07=-Q1
, -Q2
, -Q3
, -Q∑
DMD
DMD
DMD
$08=+PF1
, +PF2
, +PF3
DMD
DMD
DMD
$09=-PF1
, -PF2
, -PF3
DMD
DMD
DMD
$0A=ALL
$01=+kWh1, +kWh2, +kWh3, +kWh∑
$02=-kWh1, -kWh2, -kWh3, -kWh∑
$03=+kVAh1, +kVAh2, +kVAh3, +kVAh∑ (L&C)
$04=-kVAh1, -kVAh2, -kVAh3, -kVAh∑ (L&C)
$05=+kvarh1, +kvarh2, +kvarh3, +kvarh∑ (L&C)
$06=-kvarh1, -kvarh2, -kvarh3, -kvarh∑ (L&C)
$07=ALL
UnixTime format.
READING MODE - Convert the read
hexadecimal value in decimal format.
e.g. $522E$5FD4=1378770900
>09/09/13, 23:55:00
WRITING MODE - Convert the UnixTime
decimal value in hexadecimal format.
e.g. to set:
09/09/13, 23:55:00>1378770900=
$522E$5FD4 value to be set
$00=disabled
$01=alarm (high threshold)
$02=alarm (low threshold)
$03=pulse
Refer to the "Parameter codes" table
DMD
DMD
DMD
DMD
DMD
DMD
, A∑
DMD
DMD
DMD
DMD
DMD
DMD
DMD
, +PF∑
DMD
, -PF∑
DMD
71

Publicidad

Capítulos

Tabla de contenido
loading

Productos relacionados para Algodue ELETTRONICA UPM209

Tabla de contenido