Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

(RTU/ASCII or TCP).

6.1 MODBUS RTU/ASCII

The following tables show some writing examples in MODBUS RTU.
Values contained in Command, Query and Response messages are in hex format.
WIRING MODE SETUP
Command example: 0110203C000204000000032E29
01
-
Slave address
10
-
Function code
20
High
Starting register
3C
Low
00
High
2 words to be written
02
Low
04
-
4 data bytes
00
High
00
Low
Set 1 phase wiring mode
00
High
03
Low
2E
High
CRC
29
Low
Response example: 0110203C0002048A
01
-
Slave address
10
-
Function code
20
High
Starting register
3C
Low
00
High
2 written words
02
Low
04
High
CRC
8A
Low
DATE&TIME SETUP
Command example: 0110204A000204522E5FD43FA7
01
-
Slave address
10
-
Function code
MODBUS RTU/ASCII, TCP