MOUNTING HEIGHTS & CLEARANCE
6-3/4"
Min 28"-Max 36"
36"
DUCTING
A minimum of 5" round or 3-1/4" x 10"rectangu-
lar duct must be used to maintain maximum air
flow efficiency.
Always use rigid type metal ducts only.
Flexible ducts could restrict air flow by up to 50%.
Also use calculation (on right) to compute total
available duct run when using elbows, transitions
and caps.
ALWAYS, when possible, reduce the number or
transitions and turns. If long duct run is required,
increase duct size from 6" to 7 or 8". If a reducer
is used, install a long reducer instead of a pan-
cake reducer. Reduce duct size as far away from
opening as possible.
If turns or transitions are required:
Install as far away from opening and as far
apart, between 2, as possible.
INSTALLATION
Minimum mount height between range top to
hood bottom should be no less than 28".
Maximum mount height should be no higher
than 36".
It is important to install the hood at the
proper mounting height. Hoods mounted too
low could result in heat damage and fire haz-
ard; while hoods mounted too high will be
hard to reach and will loose its performance
and efficiency.
96"
If available, also refer range manufacturer's
height clearance requirements and recom-
mended hood mounting height above range.
*Minimum clearance of 28" hood above range
height.
** Maximum clearance 36" hood above range
height.
Minimum Duct Size:
Round:
5" minimum
Rectangular:
Requires an adaptor. Readily available at most
hardware stores.
Duct Run Calculation:
Maximum run
5" or 3-1/4" x 10" duct
Calculated Length:
each 90 Elbow used
each 45 elbow used
each 6" to 3/14 x 10"
transition used
each 3/14 x 10" to 6"
each 3/14 x 10" to 6"
transition used
Side Wall Cap w/ damper
Roof Cap
e.g.- 1 roof cap, 2x90 elbows, 1 45 elbow used:
=30' + 30' + 9' =69' used, 31' available for straight duct runs.
3
100 FT
15 FT
9 FT
1 FT
5 FT
30 FT
30 FT