Warnings
...
A0001
A0004
,
A0008 A0010
A0080
A0100
A0400
A0800
A1000
A4000
- Press ESC to hide an error message. It is displayed again after 10 seconds.
- Press STOP to acknowledge an error message or a warning message. Remove the fault. It is
recommended to check the entered data.

Extended settings of control terminals

Multifunction input
X12.3
P452 1-voltage 0...10 V
X12.4
P562 2-current 0...20 mA
3-digital NPN (active: 0 V)
4-digital PNP (active: 24 V)
5-current 4...20 mA
6-voltage, characteristic
7-current, characteristic
6-: programmable characteristic via P454...457
7-: programmable characteristic via P564...567
Refer to operating instructions manual.
P: Parameter
Digital Input/ Output
X11.6
P558 0-input (default)
1-output
logic switchable digital inputs
X11.4 P559 0-NPN (active: 0 V)
X11.5
1-PNP (active: 24V)
X11.6
X12.1
X12.2
NPN: LOW-switching (on negative signal). Default of P562.
PNP: HIGH-switching (on positive signal). Default of P559.
Applications via control terminals
Enable
X11.3
X13.3
Change
X11.4
direction of
X11.5
rotation
Set motor
X12.3
speed
Agile
Quick Start Guide
Frequency inverter overloaded. Check load behavior. Check motor parameters and
application parameters.
Overtemperature. Check cooling, fan and ambient temperature.
Max. motor temperature reached, check motoer and sensor.
Mains phase failure, check mains fuses and supply cable.
Limit frequency reached, output frequency is limited.
Input signal at X12.3 is too low. Increase the value.
Input signal at X12.4 is too low. Increase the value.
DC link voltage has reached the type- specific minimum.
Digital signals at both terminals
Start clockwise by rising edge of the signal
Start anti clockwise by rising edge of the signal
Reference speed: DC 0 ... 10 V at analog input. P452=1-voltage
(default). DC 0 V corresponds to 3,50 Hz (default value of P418).
DC 10 V corresponds to 50 Hz (default value of P419).
Multifunction output
X13.6 P550 1-digital MFO1D (P554*)
10-analog PWM MFO1A (default)
(P553*)
20-repetition frequency MFO1F
(P555*)
30-pulse train MFO1F (P557**)
Default:
1-: signal when output frequency exceeds 3 Hz (P510)
10-: output of voltage proportional to speed.
20-: frequency output 0...24 V proportional to speed
30-: output pule train, scaled by P557.
* select a signal for the output.
** Scaling
X12.3 P452 3- digital input NPN (active: 0 V)
4- digital input PNP (active: 24 V)
X12.4 P562 3- digital input NPN (active: 0 V)
4- digital input PNP (active: 24 V)