Voltage Input For External Voltage Supply - BONFIGLIOLI Vectron Agile AGL202 Guia De Inicio Rapido

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Applications via control terminals
X12.1
Select out-
put fre-
X...
quency
Data set
X11.6
change-over
X...
Protection
X12.4
function

Voltage input for external voltage supply

The external voltage supply enables the function of inputs, outputs and communication, even
if the power supply of the frequency inverter is switched off. Refer to section "technical data
of control terminals".
Data set
Parameter values can be stored in four different data sets.
If a data set is selected, the entered data is only stored in the selected data set. The other
data sets contain standard values. If no data set is selected the entered data is stored in all
four data sets.
The data sets can be switched –over via control terminals (refer to section „Function of
control terminals"). This enables the setting of different operating points of the drive or set-
tings for different motors.
Example 1: Carry out auto-tuning and enter motor data in data set 1.
DSet 4
DSet 1
Setup
DSet 0
ENT
data set
When setup is carried out the entered and measured motor data is stored in the selected
data set.
Example 2: set the motor rated voltage P370 in data set 2.
P 3702
+
P 370
P 3701
ENT
Hold
data set
05/2013
Fixed frequency change-over via two digital inputs.
Set P492=3. Set frequency values in P480 ... 483.
Select digital inputs P66 and P67.Select a frequency
value via P66 und P67.
Select digital inputs for P066 and P067:
71
X11.4
72
X11.5
73
X11.6 (P558=0)
74
X12.1
75
X12.2
76
X12.3 (P452=3 NPN or 4 PNP)
77
X12.4 (P562=3 NPN or 4 PNP)
Fixed frequency change-over via two
digital inputs. The four data sets can
Include different parameter values.
Select a data set via X11.6 and X12.1
Connect a motor thermal contact.
Set P570: 1-Warning or 2-Error switch off.
. .
.
ENT
4002 U
ENT
ENT
P370, DS 2
DS
Value of P370 in data set 2
41
P66 P67 Selection
Default
Hz
0
0
P480
1
0
P481
10
1
1
P482
25
0
1
P483
50
X11.6 X12.1
Selection
0
0
DS 1
1
0
DS 2
1
1
DS 3
0
1
DS 4
Agile
Quick Start Guide
0

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Vectron agile agl402

Tabla de contenido