Translation of the original instructions
Function
No. of
the wire
Generator
1/3
ready
OK/Secur
Earth
8
Start
9/8
Regulation
11 - /
voltage U T°
14+
Interface power
12/13
DIAGRAM OF AUTOMATION START UP
Gâchette
Mechanical
trigger
méca
relais
Outdoor
extérieur
relay
mode
Enslavement
asservissement
mode
SAFETY AND DEVICE FAILURE
- If the temperature input does not change after 5 s, the product is set to fault "E12".
- If a thermocouple breaks, then the regulation stops because the voltage U T° exceeds the maximum voltage of 4.9 V.
- f the temperature drops significantly within a short period of time (e.g. when thermocouple probes go out of order),
the heating stops and the product goes to fault "E11".
- In order to have the most accurate control possible, the measuring point(s) must be as close as possible to the inductor.
- This is the reason for the 2 thermocouples on the external interface.
- The display shows the highest temperature measured by the sensors.
WARRANTY
The warranty covers faulty workmanship for 2 years from the date of purchase (parts and labour).
The warranty does not cover:
• Transit damage.
• Normal wear of parts (eg. : cables, clamps, etc..).
• Damages due to misuse (power supply error, dropping of equipment, disassembling).
• Environment related failures (pollution, rust, dust).
In case of failure, return the unit to your distributor together with:
- The proof of purchase (receipt etc ...)
- A description of the fault reported
POWERDUCTION HEAT CONTROLER
Type
Electrical settings
Digital output
Type
Permissible direct current
Earth
Earth
Digital input
Residual voltage (open
circuit)
Input impedance
Analog input
Maximum input voltage
Input impedance
Accuracy
Continuous
Output voltage
power supply
Output impedance
500ms
500ms
500ms
Values
Logic
Dry contact
Closed
5 A 30 V
Ready-to-heat generator
Opened
Generator fault
Terre
Earth
15 V
Requires the use of a dry
contact: a closed contact
3.5 kΩ
activates the heater.
5 V
Image input of the meas-
ured temperature.
5.4 kΩ
See correspondence table
+/-5%
15 V
100 Ω
EN
17