First time start-up
(Setup wizard)
When all connections to the controller
have been made, the first time start-up can
be performed.
After switching power on, the Danfoss logo
will appear for 5 seconds
The setup wizard will start.
During the setup wizard following se-
quence must be repeated for all parameter
settings:
a) Parameter name + 1
option
st
b) Press
to highlight 1
option
st
c) Scroll with
/
to your desired
option.
d) Press
to set your choice
e) Scroll with
to next parameter (repeat
sequence a to e)
1. Language
You can select any of these 9 languages:
English, Chinese, Portuguese, Russian,
Spanish, French, Italian, German, Arabic
2. System configuration
Select any of these 5 predefined configura-
tions:
ICAD + NC(solenoid)
NC(solenoid)
AKV/A
AKV/A + NC(solenoid)
ICAD
3. Operation mode
Select any of these 3 predefined modes:
Master (EKE 347 as Master controller)
IO
(EKE 347 as In/Out module)
Slave (EKE 347 as slave for another
Master
4. Regulating principle
Select one of these 2 principles
Low
High
5. Liquid level setpoint
Type in any level setpoint from 0% to 100%
(default is 50.0%)
50.0%
6. Lower level limit
Type in any limit from 0% to 100%
(default is 15%)
15%
10
7. Upper level limit
Type in any limit from 0% to 100%
(default is 85%)
85%
8. Level signal setup
Select one of these 4 predefined signal
setup:
AKS 4100
Voltage
Current
AKS 41
9. Valve feedback setup
Select one of these 3 predefined feedback
setup (valve feedback is only possible with
ICAD):
xxxxxx
Not used
Voltage
Current
10. Common alarm setup
Select one of these 4 predefined methods:
High Alarm
D04
Disp only (only Bell symbol flashing)
D03
11. Apply wizard settings
Press
to confirm all inputs
or
Press
to return to last menu
Once data entry has been confirmed, the
controller has sufficient data to do a
qualified regulation of your system.
You are now asked to select one of these
menus.
Main menu
Main switch
I/O check
Press
for reaching the Setup & service
menu or press
Home display image.
If for some reason it is needed to run the
setup wizard again, this is possible by log
in to the setup & service menu with
commissioning authority.
DKRCI.PI.RP0.C3.ML / 520H8794
Alarm and error codes:
When detecting an alarm from external
sources or the flashing bell in the display,
the alarm description can be found as a text
message in the Status menu under Active
alarms.
Both alarms and errors will be shown here.
If more alarms/errors occur simultaneously,
they will be shown as subsequent text lines.
Alarms:
Upper level
Lower level
Standby mode
Valve B CAN ID conflict
Valve C CAN ID conflict
IO module CAN ID conflict
IO module communication
Communication to master lost
Min/max OD conflict
Common alarm HW conflict
Control method conflict
Multiple valve setup conflict
Valve C alarm
Valve B alarm
Oscillation in level signal
Valve position
Multiple valve capacity
Valve C communication
Valve B communication
Errors:
Internal error
Level signal out of range
Valve position signal out of range
Sensor supply overload
AKS 4100 error
Too much current AI3
Too much current AI4
DO4 overload
2 times for reaching the
© Danfoss A/S (DF), 2016-01