ENGLISH
Setup & service menu (Requires Log-In. Password to be assigned in Commisioning menu)
Parameter
Reference
Main switch
Liquid level setpoint
Operation mode
Alarm setup
Lower level limit
Upper level limit
Level alarm mode
Lower delay
Upper delay
Lower level hysteresis
Upper level hysteresis
Function common alarm
Oscillation detect band
Oscillation detect timeout
Force pump OFF
in stop mode
IO Lower level limit
IO Upper level limit
IO Lower level hysteresis
IO Upper level hysteresis
IO Lower delay
IO Upper delay
IO Level limit
IO Level delay
IO Level hysteresis
IO Level action
Control
Control Method
Regulating principle
P-band
Integration time Tn
Neutral zone
Difference
Period time for AKV/AKVA
Minimum OD
Maximum OD
Display
Language
Output indication
Login timeout
Backlight timeout
Password daily
Password service
Password commission
IO config
System configuration
Level signal setup
Voltage at low liquid level
Voltage at high liquid level
Current at low liquid level
Current at high liquid level
Valve position setup
Voltage at closed valve
position
Voltage at open valve
position
Current at closed valve
position
Current at open valve
position
Common alarm setup
Multiple valve setup
Multiple valve pattern
Valve A capacity
Valve B capacity
Valve C capacity
ICAD takeover OD
IO module setup
Communication CAN ID
CAN baudrate
Modbus ID
Modbus baudrate
Modbus mode
Modbus mapping
Valve B CAN ID
Valve C CAN ID
IO Mod. CAN ID
RW = Read & Write
R = Read only
(D) = Parameter is hidden if not active in the selected application
8
Options
On, Off
0 - 100%
Master, IO, Slave
0 - 100%
0 - 100%
Time, Hysteresis
0 - 999 sec
0 - 999 sec
0-20 %
0-20 %
Not follow; Follow up; Follow low; Follow all
0 - 100%
2 - 30 min
Yes / No
0 - 100%
0 - 100%
0-20 %
0-20 %
0 - 999 sec
0 - 999 sec
0 - 100%
0 - 999 sec
0-20 %
Falling,Rising
On/Off ,P, PI
Low, High
5 - 200%
60 - 600 sec
0 - 25%
0,5-25%
3-15 sec
0 - 99%
1 - 100%
EN,CN,PT,RU,SP,FR,IT, GER, ARAB
level, OD
1 - 120 min
0 - 120 min
3 -digit, 0 - 999
3 -digit, 0 - 999
3 -digit, 0 - 999
ICAD+NC, ICAD, AKV/A+NC, AKV/A, NC only
AKS 4100, AKS 41, Current, Voltage
0-10V
0-10V
0-20 mA
0-20 mA
Not used, Current, Voltage
0-10V
0-10V
0-20 mA
0-20 mA
D04, High alarm, D03, Disp only
Not used, 2 same cap, 2 dif cap, 3 same cap, 3 dif cap
Parallel,Sequence
0-100 %
0-100 %
0-100 %
0-100%
Used, Not used
1 - 127
20k, 50k, 125k, 250k, 500k, 1M
0 - 120
0, 1200, 2400, 4800, 9600, 14400, 19200, 28800, 38400
8N1, 8E1, 8N2
Operation, Setup
1 - 127
1 - 127
1 - 127
N/A = Not shown
DKRCI.PI.RP0.C3.ML / 520H8794
User level - access
Daily
Service
RW
RW
RW
RW
R
R
RW
RW
RW
RW
R
R
R
RW
R
RW
R
RW
R
RW
R
R
R
RW
R
RW
R
RW
RW
RW
RW
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW (L)
R
RW
R
RW
RW
RW
N/A
N/A
N/A
N/A
N/A
N/A
R
R
R
R
R
RW
R
RW
R
RW
R
RW
R
R
R
RW
R
RW
R
RW
R
RW
R
R
R
R
R
R
R
R
R
R
R
R
R
RW
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
(L) = Locked by Mainswitch ( Switch OFF Mainswitch for change of setting)
Default
Commissioning
values
RW
Off
RW
50.0%
RW (L)
Master
RW
15%
RW
85%
RW
Time
RW (D)
10 sec
RW (D)
50 sec
RW (D)
3%
RW (D)
5%
RW
Not follow
RW (D)
100%
RW (D)
20 min
RW
No
RW (D)
5%
RW (D)
95%
RW (D)
3%
RW (D)
3%
RW (D)
10 sec
RW (D)
50 sec
RW (D)
50%
RW (D)
10 sec
RW (D)
3%
RW (D)
Falling
RW
PI
RW
Low
RW (D)
30.0%
RW (D)
400 sec
RW (D)
2.0%
RW (D)
2%
RW (D)
6 sec
RW (D)
0%
RW (D)
100%
RW (L) (D)
EN
RW (D)
Level
RW
10 min
RW
2 min
RW
100
RW
200
RW
300
RW (L)
ICAD + NC
RW (L)
AKS4100
RW (D)
0 V
RW (D)
10 V
RW (D)
4 mA
RW (D)
20 mA
RW (L)
Not used
RW (D)
0 V
RW (D)
10 V
RW (D)
4 mA
RW (D)
20 mA
RW (L)
High alarm
RW (L)
Not used
RW (D)
Parallel
RW (L) (D)
50%
RW (L) (D)
50%
RW (L) (D)
30%
RW (D)
80%
RW (L) (D)
Not used
RW
1
RW
500k
RW
1
RW
19200
RW
8E1
RW
Operation
RW (D)
2
RW (D)
3
RW (D)
4
© Danfoss A/S (DF), 2016-01