ΔPC (bar) - Pressure head according to the temperature
Tcond – Saturated condensing temperature (°C)
-15
-40
12.8
-35
10.9
-30
8.6
-25
6.1
Table 1: determine the design pressure head ΔP from the saturated evaporating temperature Tevap and condensing temperature Tcond for the chosen refrigerant.
RATING (kW) – Equivalent cooling capacity of the CAREL valves
Tevap. -30°C
12
E2V09B
4.9
E2V11B
8.8
E2V14B
13.4
E2V18B
19.1
E2V24B
38
E2V35B
76.6
E4V55A
--
E4V65A
--
E4V85A
--
E4V95A
--
Tevap. -40°C
16
E2V09B
5.7
E2V11B
10.1
E2V14B
15.5
E2V18B
22
E2V24B
43.9
E2V35B
88.4
E4V55A
--
E4V65A
--
E4V85A
--
E4V95A
--
Table 3: the data are calculated with subcooling set at 5 °C.